Further information for Dold 0050133 IL9171.12/031 undervoltage relay 3AC400V
Technical data
1- / 3-phase
1, 3
Auxiliary voltage
Without
Enclosure design
Distribution board
Nominal voltage max.
3/N AC 500 / 290 V
Output contacts
2 C/O contacts
Width
17,5 mm
Type
IL 9171
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3AC 400 V
Response value
0,55 - 1,05 Un
Time delay
0,5 - 20 s
Approvals and Markings
CCC
Variant
Without N. NC circuit operation. Settable time delay t1. Settable response value
The Dold undervoltage relay IL9171.12/031 is an industrial relay for network monitoring in three-phase power systems. It is designed to detect undervoltages and enables automatic switching to a safety power supply or safety lighting in accordance with DIN VDE 0100-710 or DIN VDE 0108. The device is rated for a nominal voltage of 3AC 400 V and operates on the standby current principle, whereby the output relay is not activated in the event of a fault. The IL9171.12/031 variant features 2 changeover contacts as output contacts and offers an adjustable pickup value in the range of 0.55 to 1.05 times nominal voltage. The time delay t1 is also adjustable and ranges between 0.5 and 20 seconds. The width is 17.5 mm, and the device is designed for use in installation distributors, with connection terminals located at the bottom (I-type construction). It can operate without auxiliary voltage, simplifying installation and ensuring independence from additional power sources.
Applications
This relay is used in industrial and commercial facilities where reliable network monitoring is required. It protects sensitive loads from damage caused by sudden voltage drops or phase failures. Typical applications include monitoring power supplies in production plants, lighting systems, emergency power supplies, and installations certified to DIN VDE 0108. The variant with time delay t1 is particularly suitable for unstable networks, for example, in local power generation or in networks with high load, where delayed fault signaling prevents unnecessary disconnection of loads during brief voltage dips.
Functions and Features in Detail
The device detects undervoltages in three-phase networks and can also be connected single-phase, in which case terminals L1, L2, and L3 must be bridged. Measurement is performed via the arithmetic mean of the phase voltages; for variants without neutral conductor connection, L1 and L3 are measured against L2 (IK/SK 9171) or L1 and L2 against L3 (IL/SL 9171). The LED indicator signals the state of the output relay – the yellow LED lights up when the contact is activated. Phase sequence is arbitrary, which enhances installation flexibility. The hysteresis is approximately 4 %, ensuring stable switching behavior.
Technology Explained Simply
The relay operates without auxiliary voltage, meaning it is directly connected to the network to be monitored and draws its power from it. The standby current principle ensures that the output relay is not activated under normal conditions – it only switches when a fault is detected. The time delay t1 prevents immediate fault signaling during brief voltage dips, which is particularly useful in unstable networks. The adjustable pickup voltage allows individual adaptation to the specific conditions of the respective network.
Compatibility and Accessories
The device is suitable for single- and three-phase connections and can be used in various network voltages, with a maximum nominal voltage of 3/N AC 500 / 290 V. It is compatible with other variants of the IL series, for example, models featuring phase sequence detection or a time delay t2 for returning to normal operation. The width of 17.5 mm allows mounting in standard installation distributors according to DIN 43 880.
Mounting and Installation
Mounting is performed in installation distributors with terminals located at the bottom. The depth is 59 mm. The terminals are designed for cable connections, and the devices are suitable for frequencies between 45 and 65 Hz. Installation requires no additional auxiliary voltage, simplifying wiring.
Operational Advantages
The relay provides reliable network monitoring without requiring additional power supply. Adjustable parameters such as pickup value and time delay allow flexible adaptation to different requirements. The LED indicator facilitates diagnostics during operation. The standby current principle ensures clear state indication and prevents false alarms during brief disturbances. The width of 17.5 mm and I-type construction make it compatible with common distributors in industrial and commercial applications.
Approvals and Markings
The device complies with the standard IEC/EN 60255-1 and carries the CCC approval. It is designed for use in industrial and commercial facilities that require high reliability and safety standards.