Further information for Dold 0049270 undervoltage relay IK9171.11/2003AC400/230V
Technical data
1- / 3-phase
1, 3
Auxiliary voltage
Without
Enclosure design
Distribution board
Nominal voltage max.
3/N AC 500 / 290 V
Output contacts
1 C/O contact
Width
17,5 mm
Type
IK 9171
Operate delay
Variant
Contact equipping
1 changeover contact
Nominal voltage
3/N AC 400 / 230 V
Response value
0,7 / 0,74 Un
Time delay
without
Approvals and Markings
UKCA
Variant
With N. NC circuit operation. Without time delay. Fixed response value
The Dold undervoltage relay IK9171.11/2003AC400/230V,7/0,74UN is designed for monitoring three-phase power networks for undervoltage and enables automatic switching to a safety power supply or safety lighting in accordance with DIN VDE 0100-710 or DIN VDE 0108. It is designed for use in industrial and installation distributors and operates on the no-current principle, whereby the output relay is not activated in the event of a fault. The width is 17.5 mm, and the device is manufactured in I form, with connection terminals located at the bottom for installation and industrial distributors in accordance with DIN 43 880.
Applications
This relay is used for network monitoring in three-phase systems and can also be connected in single-phase mode. It is particularly suitable for applications where a secure power supply for emergency lighting or safety functions must be ensured in the event of undervoltage or phase failure. The version without time delay is suitable for systems where immediate contact switching is required upon detection of a fault.
Functions and equipment in detail
The device detects undervoltages in three-phase networks and responds at a pickup value of 0.7 to 0.74 times the nominal voltage (Un). The contact configuration includes a changeover contact, which opens the 11-14 contact when a fault is detected. An LED indicator signals the contact position – when the output relay is activated, the LED lights up yellow. Phase sequence is arbitrary, allowing flexible installation. The device operates without auxiliary voltage and is therefore independent of additional power supplies.
Technology explained simply
Measurement is performed via the arithmetic mean of the individual phases against the neutral conductor (N). For variants without neutral conductor connection, L1 and L3 are measured against L2 (IK/SK 9171) or L1 and L2 against L3 (IL/SL 9171). In single-phase operation, terminals L1, L2, and L3 must be bridged. The hysteresis is approximately 4%, ensuring stable switching behavior during network voltage fluctuations. The nominal voltage is 3/N AC 400/230 V, with a maximum nominal voltage of 3/N AC 500/290 V. The frequency range is between 45 and 65 Hz.
Compatibility and accessories
The relay is suitable for 1- or 3-phase connections and can be integrated into installation distributors in accordance with DIN 43 880. It is part of the IK 9171 product family, which also includes variants with time delays t1 and t2 as well as phase sequence detection. The width of 17.5 mm allows for compact mounting in standard distributors. The devices are manufactured in accordance with IEC/EN 60255-1 and carry the UKCA mark.
Mounting and installation
Mounting is performed in installation distributors with terminals located at the bottom. The depth is 59 mm. The terminals are designed for direct connection to cables. In single-phase operation, terminals L1, L2, and L3 must be connected. Installation is performed without additional auxiliary voltage, simplifying wiring.
Advantages in operation
The relay provides reliable network monitoring without auxiliary voltage and with low power consumption (approx. 6 VA). The LED indicator allows for quick visual control of the operating status. The no-current principle ensures that the output relay is not unintentionally activated in the event of a fault. The compact design with a width of 17.5 mm enables flexible integration into existing distributor structures. Compliance with standards IEC/EN 60255-1 and DIN VDE 0100-710 ensures safety and reliability in operation.