| Technical data |
| Classification | Temperaturüberwachung |
| Enclosure design | Switch cabinet |
| Measuring range max. | 100 °C |
| Output contacts | 1 C/O contact, 1 NO contact |
| Width | 45 mm |
| Type | BA 9094 |
| Variant |
| Auxiliary voltage | AC 230 V |
| Contact equipping | 1 changeover contact for P1, 1 NO contact for P2 |
| Response value / Reset value P1 | only response value |
| Response value / Reset value P2 | only response value |
| Response value P1 = P2 | 60 - 150 C |
| Variant | 1 PT 100 input. 2 outputs. Seperate adjustable response and release value for every output |
The temperature monitor BA 9094.28/100 AC230V P1=60-150C from Dold is an industrial monitoring relay of the VARIMETER series, specifically designed for temperature monitoring in applications such as motors, ball bearings, or rooms. The reset values are not adjustable, as this variant only supports trigger values. The auxiliary voltage is AC 230 V, and the device is designed for use in enclosures. The width of 45 mm allows for compact mounting in standard control panels.
Applications
The temperature monitor is suitable for continuous monitoring of operating temperatures in industrial systems. It is particularly used in motors, bearings, and rooms where overheating or sensor failure must be detected and signaled. The 2-wire technology enables simple installation, as PT100 sensors are connected via two wires. Wire break detection ensures that a broken sensor or wiring fault is also recognized as an error.
Functions and equipment in detail
The device features two outputs: a changeover contact for the first switching point (P1) and a make contact for the second switching point (P2). The trigger values for both outputs are adjustable in the range of 60 °C to 150 °C. The hysteresis, i.e., the difference between trigger and reset value, is 85 % to 95 % of the set trigger value. The outputs operate on the rest current principle, meaning the relay is activated during normal operation and de-energizes when the trigger value is exceeded or in case of wire break. This enables clear error indication via the output contacts.
Technology explained simply
Temperature measurement is performed via a PT100 sensor, which functions as a resistance thermometer. As temperature increases, the sensor's resistance rises, which is detected by the relay. When the set trigger value is reached, the relay de-energizes. LED indicators (red for fault, green for operation) visually signal the status. The auxiliary voltage of AC 230 V powers the device, with a rated consumption of 3.4 VA. The operating temperature of the device ranges from -20 °C to +60 °C, and the storage temperature ranges from -25 °C to +70 °C.
Compatibility and accessories
The device is designed for use with PT100 sensors connected in 2-wire technology. It is equipped with a single PT100 input, which can control two separate outputs, each with its own trigger value. The use of additional relays or switching devices for further signal processing is possible, but not part of the device.
Mounting and installation
The temperature monitor is mounted in enclosures and requires a width of 45 mm. The connection terminals are clearly labeled: A1 and A2 for auxiliary voltage, P0, P1, P2 for PT100 sensors, and 11-12-14 for the changeover contact and 23-24 for the make contact. Mounting is for continuous operation, and the maximum operating altitude is 2000 m above sea level. The electrical life at 5 A and AC 230 V exceeds 0.1 million switching operations.
Advantages in operation
The separate adjustment of trigger values for the two outputs enables flexible use, e.g., for different alarm levels. Wire break detection increases reliability by recognizing mechanical faults. Clear signaling via LEDs and a mechanical life of over 30 million switching operations ensure long service life. Compliance with the standard IEC/EN 60255-1 ensures reliability in industrial applications.