Further information for Dold 0048873 IK9171.11/041 undervoltage relay 3AC400V
Technical data
1- / 3-phase
1, 3
Auxiliary voltage
Without
Enclosure design
Distribution board
Nominal voltage max.
3/N AC 500 / 290 V
Output contacts
1 C/O contact
Width
17,5 mm
Type
IK 9171
Operate delay
Variant
Contact equipping
1 changeover contact
Nominal voltage
3AC 400 V
Response value
0,55 - 1,05 Un 4%
Time delay
0,5 - 20 s
Approvals and Markings
UKCA
Variant
Without N. NC circuit operation. Settable time delay t2. Settable response value
The Dold undervoltage relay type IK9171.11/041 is an electrical monitoring device for detecting undervoltage in three-phase power networks. It is used for network monitoring and enables automatic switching to a safety power supply or safety lighting in accordance with DIN VDE 0100-710 and DIN VDE 0108. The device operates on the rest current principle, in which the output relay is not activated in the event of a fault, and is designed for use in installation distributor configurations. The width is 17.5 mm, allowing it to be integrated into standard distributor boxes in accordance with DIN 43 880.
Applications
This relay is used in industrial and commercial installations where reliable network monitoring is required. It is particularly suitable for applications in which certain consumer groups must be switched off during voltage dips or phase failures and re-energized after a defined waiting period. This applies, for example, in unstable power networks, such as those found in local power generation or in networks of the 2nd and 3rd world. It is also suitable for consumers that must not be re-energized immediately after a short power failure – such as compressors or certain processing machines.
Functions and equipment in detail
The device monitors three-phase networks for undervoltage and can also be connected single-phase. The rated voltage is 3AC 400 V, with a maximum rated voltage of 3/N AC 500/290 V. The pickup value is adjustable within a range of 0.55 to 1.05 times the rated voltage, with a hysteresis of approximately 4 %. The time delay t2 for returning to the normal state is adjustable between 0.5 and 20 seconds. The contact configuration includes a changeover contact, which is used for controlling auxiliary functions or safety circuits. A yellow LED indicates the contact position – it lights up when the output relay is activated (contacts 11-14 closed).
Technology explained simply
The relay measures the arithmetic mean of each phase against the neutral conductor (N). In variants without a neutral conductor connection, L1 and L3 are measured against L2 (for IK/SK 9171) or L1 and L2 against L3 (for IL/SL 9171). In single-phase connection, the terminals L1, L2, and L3 must be connected together. The time delay t1 is only effective if the phase voltage L1-N (IK/SK 9171) or L3-N (IL/SL 9171) is at least 0.5 times the rated voltage. After switching on the operating voltage, the device initially enters the normal state, even if a fault is present. It only switches to the fault state after the time delay t1 has elapsed. The function is certified in accordance with IEC/EN 60255-1 and bears the UKCA mark.
Compatibility and accessories
The device is suitable for 1- or 3-phase connections and can operate without auxiliary voltage. It is designed in I form, which has a depth of 59 mm and bottom-mounted terminals for installation and industrial distributors in accordance with DIN 43 880. The width of 17.5 mm allows mounting in standard distributor boxes. It is not equipped with a neutral conductor connection and operates on the rest current principle. The time delay t2 is adjustable, as is the pickup value.
Mounting and installation
Mounting is carried out in installation distributor boxes in accordance with DIN 43 880. The terminals are located at the bottom, enabling easy integration into existing switchgear. The mounting width of 17.5 mm corresponds to the standard for modular components. The frequency range coverage is between 45 and 65 Hz. The overload capacity is 1.15 times the rated voltage continuously. The rated consumption values are approximately 6 VA for the IK/SK 9171.11 variant.
Advantages in operation
The relay provides reliable and low-maintenance network monitoring without auxiliary voltage. The adjustable pickup values and time delays allow application-specific adaptation. The LED indicator facilitates diagnosis of the operating state. The form factor is optimized for use in installation distributor boxes, ensuring compact and secure mounting. Compliance with standards IEC/EN 60255-1 and DIN VDE 0100-710 ensures conformity with applicable safety requirements.