| Technical data |
| Enclosure design | Switch cabinet |
| Output contacts | 2 C/O contacts |
| Time function(s) | Fleeting on make |
| Width | 22,5 mm |
| Type | MK 9989 |
| Variant |
| Contact equipping | 2 contacts fleeting on make (changeover), |
| Nominal voltage | AC/DC 24 V + AC 220 - 240 V |
| Time range | 0,5 - 10 s |
| Variant | 2 fleeting make |
The Dold wipe relay MK9989AC/DC24V+AC220-240V0,5-10S is an industrially usable
on-delay wipe relay with a width of 22.5 mm, specifically designed for use in enclosures. It is used for time-controlled switching of electrical loads, where the switching function occurs after an adjustable delay time. The device features a
dual-voltage design, enabling operation with a nominal voltage of AC/DC 24 V as well as AC 220–240 V. The time function is continuously adjustable within a range of 0.5 to 10 seconds, with adjustment performed on an absolute scale, ensuring precise and reproducible time control. The repeatability accuracy is less than ±0.5 % of the scale end value, making it suitable for applications requiring high precision.
Applications include the control of drives, lighting systems, pumps, or other electrical consumers where a time-delayed switching function is required. The relay is designed for use in industrial environments demanding high operational safety and reliability. The operating temperature ranges from -20 °C to +60 °C, allowing use even in climatically demanding installations. Storage is possible within a range of -25 °C to +70 °C.
Functions and equipment in detail include two
on-delay wipers (changeover contacts) as output contacts, each providing one normally open and one normally closed contact. The contacts are made of AgSnO₂, a material known for its high switching durability and low wear. The rated operating voltage is AC 250 V, and the thermal current Ith is 5 A. The relay is designed for continuous operation and features a mechanical life of over 30 million switching operations. The electrical life is at least 500,000 switching operations at 3 A and AC 230 V. The permissible switching frequency is 6000 switching operations per hour.
Technology explained simply shows that the relay maintains a delay time after the operating voltage is switched on, before the contacts switch. The time delay is achieved by a mechanical wiper moving along a scale. Adjustment is done manually on the absolute scale, ensuring precise reproducibility. The drop-out voltage is 15 % of the nominal voltage, meaning the relay remains stable even with slight voltage fluctuations. Voltage influence values are ≤1 %, and temperature influence is ±0.1 % per Kelvin, ensuring high stability under varying operating conditions.
Compatibility and accessories include control via two-wire initiators, facilitating integration into existing control systems. The terminal clamps are designed for secure connections, and terminal markings follow the standard A1, A3(+), A2 for the operating voltage, and 15–18 and 21–24 for the output contacts. The enclosure protection rating is IP 40, and the terminals are IP 20, providing protection against touch and dust, but not against water or splashing water. The enclosure is made of a thermoplastic with V0 behavior according to UL Subject 94, indicating a high flame retardancy class.
Mounting and installation is carried out in standard enclosures with a width of 22.5 mm. Mounting is done via screw fastening, with vibration resistance according to IEC/EN 60068-2-6, with an amplitude of 0.35 mm and a frequency of 10 to 55 Hz. Climate resistance is specified as 20/060/0, highlighting suitability for industrial environments.
Operational advantages include high repeatability accuracy, robust construction, and simple adjustability. Integrated LED indicators signal operational readiness (upper LED) and activated contact position (lower LED), facilitating diagnostics during operation. Compliance with the standard IEC/EN 61812-1 ensures conformity with international standards for time relays. The overvoltage category III and insulation test voltage of 2.5 kV guarantee high electrical safety. EMC requirements according to IEC/EN 61000-4-2 to -4-6 are met, ensuring immunity against electromagnetic interference. Radio frequency interference suppression complies with limit class B according to EN 55011, which is relevant for use in industrial installations.
The device is designed for use in enclosures and meets requirements for reliability, safety, and ease of maintenance in industrial control systems. The combination of mechanical robustness, high accuracy, and simple handling makes it a suitable component for time-controlled applications in automation technology.