| Technical data |
| Enclosure design | Switch cabinet |
| Output contacts | 2 C/O contacts |
| Time function(s) | Off-delay, with control signal |
| Width | 22,5 mm |
| Type | MK 9962 |
| Variant |
| Contact equipping | 2 changeover contacts delayed |
| Nominal voltage | AC/DC 24 V + AC 220 - 240 V |
| Time range | 0,15 - 3 s |
| Variant | Release delay, with control signal |
The Dold MK9962 is a delayed-release time relay of the MINITIMER series, designed for industrial control applications. It features a dual-voltage configuration with nominal voltages AC/DC 24 V and AC 220–240 V, enabling flexible use in various systems. The time function is delayed-release with control signal, meaning the relay energizes and closes the output contacts upon activation of the control signal. Once the control signal is removed, a time-controlled release behavior begins, during which the contacts return to their resting position after the set delay time has elapsed. The delay time is continuously adjustable via a rotary switch in the range of 0.15 to 3 seconds, with adjustment indicated on an absolute scale. The repeatability is ≤ ±1 %, ensuring high precision in repeated switching operations.
Applications
This time relay is suitable for time-dependent controls in industrial systems, for example, to delay switching operations for pumps, motors, or lighting systems. It is frequently used in enclosures where a compact design and clear signal indication are required. The device is intended for continuous operation, with an operating temperature range from -20 °C to +60 °C. The operating altitude is limited to a maximum of 2000 m above sea level.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, sufficient for controlling multiple loads. The contact operation is delayed, meaning the contact change occurs only after the set time has elapsed. The contacts are made of AgSnO₂, a material suitable for high switching life and low contact resistance. The rated operating voltage is AC 250 V, and the thermal current Ith is specified as 5 A. The electrical life at 5 A and AC 230 V is 500,000 switching operations, while the mechanical life is 30 million switching operations. The permissible switching frequency is 6000 switching operations per hour.
Technology Explained Simply
Control is performed via potential-free terminals B1 and B2. These are electrically connected to the voltage terminals A1–A3 and therefore require galvanic isolation if voltage is applied to A1–A3. The control signal is supplied via a potential-free contact, for example, from a pushbutton or another relay. The operating voltage is connected to terminals A1–A2 (AC 220–240 V) and A3–A2 (AC/DC 24 V). The minimum switching-on time is 20 ms, and the rearm time is approximately 5 ms. The voltage influence is ≤ ±0.5 %, and the temperature influence is < ±0.1 %/K, indicating high stability under varying operating conditions.
Compatibility and Accessories
The relay is designed for use in enclosures and complies with standard EN 61812-1. The housing design is intended for enclosure mounting, with a width of 22.5 mm. The connection terminals are clearly labeled: A1–A3 for operating voltage, B1–B2 for control input, and 15–18 and 25–26/28 for the two changeover contacts. Indication is provided by two LEDs: the upper LED lights up when the control contact is connected, and the lower LED indicates activation of the output relay. This enables easy fault diagnosis.
Mounting and Installation
Mounting is performed in standard enclosures with a width of 22.5 mm. The terminals are designed for secure connections, with control inputs B1–B2 to be operated potential-free. The connection terminals are clearly labeled to prevent incorrect connections. The operating voltage is connected to A1–A2 (AC 220–240 V) and A3–A2 (AC/DC 24 V). The delay time is adjusted via the continuous rotary switch, which is read on an absolute scale.
Operational Advantages
The MK9962 offers simple operation and clear signal indication via the two LEDs. The high repeatability and long contact life ensure reliable operation. The dual-voltage configuration increases flexibility when integrating into existing systems. Galvanic isolation of the control inputs is not provided; therefore, control must be potential-free, which must be considered during planning. EMC requirements are met, including immunity to electrostatic discharge, high-frequency radiation, and fast transients, ensuring reliability in industrial environments.