Further information for Dold 0044746 BA9043/001 undervoltage relay 690V
Technical data
1- / 3-phase
3
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
3/N AC 690 / 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9043
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3AC 690 V
Time delay
without
Approvals and Markings
UKCA
Variant
For 3p3w systems
The undervoltage relay BA9043/001 from Dold is a 3-phase monitoring device for three-phase AC networks without a neutral conductor. It is designed for continuous monitoring of network voltage and automatically disconnects in case of undervoltage or voltage loss, protecting connected devices or systems from damage. The device is rated for nominal voltages of 3AC 690 V and is suitable for industrial applications as well as railway installations, where reliable voltage monitoring is required.
Applications
This relay is used in industrial enclosures to ensure the operational safety of machines, drives, or entire production systems. It monitors 3-phase AC networks in the frequency range of 50 to 400 Hz. The design is intended for installation in enclosures, with a width of 45 mm, enabling compact mounting.
Functions and Features in Detail
The device monitors voltage via arithmetic mean measurement. For the BA9043/001 variant, designed for networks without a neutral conductor, phases L1 and L2 are measured against L3. The pickup and dropout values are adjusted using rotary potentiometers on the front of the device, allowing user-friendly and precise adaptation to specific applications. The pickup value is continuously adjustable between 0.85 and 1.05 of the nominal voltage, and the hysteresis (dropout ratio) ranges from 0.75 to 0.95 of the pickup value. The time delay is not present in this variant, meaning the relay reacts immediately upon undervoltage.
Technology Explained Simply
The relay operates on the standby current principle, where the output relay remains inactive in the event of a fault and stays in its resting state. This prevents unwanted switching operations and increases reliability. LED indicators show operational readiness (red LED) and contact position (green LED), simplifying diagnosis of operating states and faults. The device is harmonic-insensitive, meaning it functions reliably even during network disturbances caused by harmonic overvoltages. The operating temperature range is -20 °C to +60 °C, and the storage temperature range is -25 °C to +60 °C.
Compatibility and Accessories
The relay is suitable for networks with frequencies from 50 to 400 Hz and complies with the standard IEC/EN 60255-1. It is designed for three-phase networks without a neutral conductor and can be used in systems with or without a neutral conductor, depending on the variant. The contact configuration includes 2 changeover contacts, suitable for switching operations in AC 15 and DC 13 applications. The maximum switching capacity is 2 A at AC 230 V (make contact) and 1 A at AC 230 V (break contact). The electrical life expectancy is 2 x 10⁵ switching operations at 3 A and AC 230 V.
Mounting and Installation
The device is mounted on a DIN rail, with terminals complying with DIN 46228-1/-2/-3/-4. The connection cross-sections are 2 x 2.5 mm² for rigid conductors or 2 x 1.5 mm² for stranded conductors with sheathing. The terminals are equipped with self-clamping terminal blocks, to be tightened with a torque of 0.8 Nm. Installation is carried out in enclosures, with an operating altitude up to 2000 m above sea level.
Operational Advantages
Preventive maintenance and rapid fault localization increase productivity. The LED indicators enable visual monitoring of the operating status, and the simple adjustment via rotary potentiometers reduces commissioning time. The device is designed for continuous operation and has a mechanical life expectancy of over 30 x 10⁶ switching operations. The overvoltage category III and EMC testing according to IEC/EN 61000-4-2 to -4-5 ensure high immunity to interference.
Approvals and Markings
The device carries the UKCA marking and complies with the requirements of standard IEC/EN 60255-1. The rated impulse withstand voltage is 6 kV at pollution degree 2, ensuring high insulation strength. The short-circuit withstand capability is protected by a maximum fuse rating of 4 A gG/gL.