Dold 0035352, EAN: 4030641353520

Dold 0035352 BA9043/001 3AC50-400Hz 110V undervoltage relay

Industrial Material > Industrial relays and contactors > Switching units / measuring, control relay

Dold 0035352 BA9043/001 3AC50-400Hz 110V undervoltage relay

Lieske Part No. 1312746
Mfg Part No 0035352
EAN-Code 4030641353520
Manufacturer Dold
Here only 270,07 EUR
321,38 EUR incl. VAT

Further information for Dold 0035352 BA9043/001 3AC50-400Hz 110V undervoltage relay

Technical data
1- / 3-phase3
Auxiliary voltageWithout
Enclosure designSwitch cabinet
Nominal voltage max.3/N AC 690 / 400 V
Output contacts2 C/O contacts
Width45 mm
TypeBA 9043
Operate delayYes
Variant
Contact equipping2 changeover contacts
Nominal voltage3AC 110 V
Time delaywithout
Approvals and MarkingsUKCA, CCC
VariantFor 3p3w systems
The Dold undervoltage relay BA9043/001 3AC50-400Hz 110V is a 3-phase monitoring device for three-phase AC networks without a neutral conductor. It is designed for continuous monitoring of the supply voltage and de-energizes output contacts in case of undervoltage to prevent damage to connected devices. The device is rated for nominal voltages of 3 AC 110 V and can be used in networks with frequencies from 50 to 400 Hz. Measurement is performed via arithmetic mean calculation, where phases L1 and L2 are measured against L3, as no neutral conductor connection is available. Device settings are adjusted via rotary potentiometers on the front panel, allowing the pickup and dropout values to be continuously adjusted between 0.85 and 1.05 of the nominal voltage, with a hysteresis of 0.75 to 0.95 of the pickup value.

Applications
This relay is designed for industrial applications and railway applications. It monitors 3-phase AC networks and is particularly suitable for systems where stable voltage supply is critical. The device is installed in enclosures and has a width of 45 mm, allowing integration into standard DIN rail mounting. The operating temperature range is from -20 °C to +60 °C, and the storage temperature range is from -25 °C to +60 °C.

Functions and Equipment in Detail
The device operates on the zero-current principle, meaning the output relay is not activated in the event of a fault. The output contacts consist of two changeover contacts, designed for switching operations with a thermal current of up to 6 A per contact. Switching capacities are 2 A / AC 230 V for closing contacts and 1 A / AC 230 V for opening contacts according to IEC/EN 60947-5-1. The electrical life expectancy is at least 200,000 switching operations at 3 A and AC 230 V, while the mechanical life expectancy exceeds 30 million switching operations. Indication is provided via LEDs: a red LED indicates that supply voltage is present, and a green LED signals the activated state of the output relay.

Technology Explained Simply
Voltage measurement is performed by arithmetic mean calculation of the three phases. In the variant without a neutral conductor (BA9043/001), phases L1 and L2 are measured against L3 to determine the mean value. The pickup delay is active, but no time delay is available for this variant. The overload capacity is 1.2 times the nominal voltage continuously. The nominal power consumption is 4 VA. The device is insensitive to harmonics, meaning it operates reliably even with supply voltages containing harmonic distortions. The frequency tolerance is ±5 %.

Compatibility and Accessories
The relay is available for networks with or without a neutral conductor, with the BA9043/001 variant specifically designed for systems without a neutral conductor. It is compliant with IEC/EN 60255-1 and carries the UKCA and CCC certifications. Mounting is on DIN rails according to IEC/EN 60715. The connection terminals are designed for 2 x 2.5 mm² rigid or 2 x 1.5 mm² flexible conductors with heat shrink tubing, with a stripping length of 10 mm. Fixing is done using M3.5 plus-minus screws with self-lifting inserts, with a torque of 0.8 Nm.

Mounting and Installation
Installation is carried out in enclosures on DIN rails. The connection terminals are clearly labeled: L1, L2, L3 for the supply connections and 11, 12, 14 as well as 21, 22, 24 for the two changeover contacts. Adjustment of pickup and dropout values is performed via the rotary potentiometers on the front panel. The LED indicators allow for quick visual inspection of the operating status. The operating altitude is limited to a maximum of 2000 m above sea level.

Advantages in Operation
The continuous adjustability of pickup and dropout values, as well as the hysteresis, allows the device to be adapted to different requirements. The LED indicators enable quick fault localization. The zero-current principle ensures that no unwanted activation of the output contacts occurs in the event of a fault. Insensitivity to harmonics increases reliability in networks with non-sinusoidal voltage waveforms. Compliance with the IEC/EN 60255-1 standard and the UKCA and CCC certifications ensure suitability for use in various markets.
This is an offer of: