Dold 0032367, EAN: 4030641323677

Dold 0032367 AD5998AC50/60HZ230V surge relay

Industrial Material > Industrial relays and contactors > Industrial Timers

Dold 0032367 AD5998AC50/60HZ230V surge relay

Lieske Part No. 885738
Mfg Part No 0032367
EAN-Code 4030641323677
Manufacturer Dold
Here only 351,58 EUR
418,38 EUR incl. VAT

Further information for Dold 0032367 AD5998AC50/60HZ230V surge relay

Technical data
Alarm inputs3
Alarm inputs extendable up to303
Enclosure designSwitch cabinet
Operating principleEnergized on trip
Width45 mm
TypeAD 5998
Optional buzzerYes
Variant
Nominal voltageAC 230 V
The Dold fault indicator relay AD5998AC50/60HZ230V is an industrial control device for the display and processing of fault messages in plants and buildings. It serves as a base unit for an expandable fault monitoring system designed as a new value indicator according to DIN 19235. The device is mounted in enclosures and has a width of 45 mm, making it suitable for standard control panels. The rated voltage is AC 230 V at a rated frequency of 50/60 Hz, with the operating principle based on the current flow principle – meaning the device responds to current flow during operation, not to interruptions.

Applications

The AD5998 is used in industrial monitoring technology to visually and acoustically indicate faults in machines, plants, or buildings. It is designed for continuous operation and is suitable for applications requiring rapid detection and acknowledgment of errors. Integration into larger systems is achieved via expansion units, enabling the number of fault input channels to be increased from 3 to up to 303.

Functions and Equipment in Detail

The device features three fault input channels (S1–S3), each monitoring a fault message. A light indicator can be connected for each message. Additionally, there are button terminals for acknowledging light indicators, for acknowledging horns, and for a lamp test. These functions enable targeted and controlled feedback to the operator. The device has two relay outputs: one for the collective alarm (terminals 27/28) and one for the sound alarm (terminals 13/14). The outputs are rated up to AC 230 V 3 A for the collective alarm and 2 A for the sound alarm. For higher switching capacities, a contactor must be inserted.

Technology Explained Simply

The current flow principle means the device activates when current is flowing – in contrast to relays that respond to current interruption. The fault input channels detect impulses with a minimum duration of 100 ms. Acknowledgment is triggered by an impulse lasting more than 200 ms. Power supply is via AC 230 V, with a rated consumption of 6 VA. The operating temperature range is from -20 °C to +60 °C, and storage is also possible within this range. The operating altitude is limited to a maximum of 2000 m above sea level.

Compatibility and Accessories

The AD5998 can be combined with the expansion unit AD5992, which provides six additional fault input channels. This allows system scaling to process up to 303 inputs. Expansion is achieved via a serial bus connection, with standardized terminal designations and connection options. The devices are designed for mounting on a DIN rail (DIN-EN 60715).

Mounting and Installation

Mounting is carried out in enclosures on a DIN rail. Connections are made via flat terminals with self-lifting connection washers, suitable for conductor cross-sections of 2 x 2.5 mm² (solid) or 2 x 1.5 mm² (stranded wire with ferrule). The tightening torque is 0.8 Nm. Terminal labeling follows EN 50005. The devices are designed for use in industrial environments, with enclosure protection rating IP 40 and terminal protection rating IP 20 according to IEC/EN 60529.

Advantages in Operation

The system provides a clear, structured display of faults with the option for targeted acknowledgment. Expandability allows flexible adaptation to growing requirements. The integrated relay outputs for collective alarm and sound alarm reduce the need for additional components. Compliance with DIN 19235 ensures compatibility with existing monitoring systems. EMC requirements (e.g., ESD, HF radiation, fast transients) are met according to IEC/EN 61000-4-2 to -4-5, ensuring reliability in electromagnetically demanding environments.