Technical data
ClassificationThermistor-Motorschutz
Enclosure designSwitch cabinet
Measuring range max.> 3 kΩ
Output contacts2 C/O contacts
Width22,5 mm
TypeMK 9052
Variant
Auxiliary voltageAC 230 V
Contact equipping2 changeover contacts
VariantWith electro magnetic reclosing interlock (manual reset function)
The Dold motor protection relay MK9052.12/100AC50/60HZ230V is a thermistor-based motor protection device used to prevent thermal overload of motors in industrial applications. It monitors the temperature of electric motors via special thermistors (PTC resistors) and switches off the motor when a critical resistance value is reached. The device operates on the no-current principle, where the output relay is not activated in the event of a fault, ensuring safe disconnection. The auxiliary voltage is AC 230 V, and the width of 22.5 mm allows for compact installation in enclosures. The contact configuration includes 2 changeover contacts, which can be used for controlling auxiliary circuits or signal indication.

Applications
This motor protection relay is designed for use in industrial plants where motors may be thermally overloaded due to high switching frequency, heavy starting, single-phase operation, impaired cooling, or high ambient temperatures. It protects motors from damage caused by overheating and extends the service life of drive technology. The device is installed in enclosures, mounted on a DIN rail. The operating temperature ranges from -20 °C to +60 °C, enabling use in a wide range of environments.

Functions and Equipment in Detail
The device features an input for thermistors or bimetal contacts and detects wire breaks in the sensor circuit to avoid false alarms. The pickup value is ≥ 3 kΩ, and the drop-out value is ≤ 1.8 kΩ. Up to six temperature sensors can be connected in series, allowing flexible adaptation to different motor sizes and requirements. An LED indicates the relay’s switching state. The MK9052.12/100 variant is equipped with an electromechanical re-energizing lockout, enabling a manual reset function. This means that after a shutdown, the relay does not automatically restart but must be re-energized manually by pressing a button on the front panel.

Technology Explained Simply
The relay operates on the no-current principle, where the measuring circuit consumes minimal current during normal operation. When the resistance of the thermistors exceeds the pickup value of 3 kΩ, the output relay is de-energized and disconnects the motor supply. The measuring circuit load is approximately 1 mW at a resistance of 1.5 kΩ, and the measuring voltage is about 1.2 V. The output contacts are configured as 2 changeover contacts, with a pickup delay of less than 20 ms and a drop-out delay of less than 15 ms. The electrical life expectancy is over 800,000 switching cycles at 3 A and AC 230 V, while the mechanical life expectancy exceeds 20 million switching cycles.

Compatibility and Accessories
The device is compliant with IEC/EN 60947-8 and can be operated with thermistors or bimetal contacts. The auxiliary voltage is AC 230 V, and the nominal frequency is 50/60 Hz. The switching capacity is 3 A/AC 230 V for closing contacts and 1 A/AC 230 V for opening contacts. The maximum short-circuit withstand requires a fuse of 4 A gG/gL. The terminal connections are designed for conductor cross-sections of 2 x 2.5 mm² (solid) or 2 x 1.5 mm² (stranded wire with ferrule). The terminals are secured using flat terminals with self-lifting connection washers.

Mounting and Installation
Mounting is done on a DIN rail (IEC/EN 60715) inside the enclosure. The tightening torque for the terminals is 0.4 Nm. The device dimensions are 22.5 mm (width) x 82 mm (height) x 99 mm (depth). The enclosure protection rating is IP 40, and the terminals are rated IP 20. The operating altitude is limited to below 2000 m. The devices are designed for continuous operation and meet electromagnetic compatibility (EMC) requirements according to IEC/EN 61000-4-2 to -4-6. Radio frequency interference suppression complies with Class B limits per EN 55011.

Operational Advantages
The motor protection relay provides reliable monitoring of motor temperature and prevents damage from thermal overload. Wire break detection minimizes false alarms, and the re-energizing lockout ensures safe restart. The compact design and DIN rail mounting simplify installation in existing enclosures. The long service life and high switching durability ensure low-maintenance operation. The LED indicator allows quick status checks without additional measuring instruments.
This is an offer of: