Dold 0029922, EAN: 4030641299224

Dold 0029922 voltage relay BA9036 DC127V + RV D.FOLG.POS.

Dold 0029922 voltage relay BA9036 DC127V + RV D.FOLG.POS.

Lieske Part No. 1002190
Mfg Part No 0029922
EAN-Code 4030641299224
Manufacturer Dold
Here only 233,82 EUR
278,25 EUR incl. VAT

Further information for Dold 0029922 voltage relay BA9036 DC127V + RV D.FOLG.POS.

Technical data
1- / 3-phase1
Auxiliary voltageWithout
Enclosure designSwitch cabinet
Nominal voltage max.AC 400 V
Output contacts2 C/O contacts
Width45 mm
TypeBA 9036
Operate delayYes
Variant
Contact equipping2 changeover contacts
Nominal voltageDC 127 V
Time delaywithout
Approvals and MarkingsCCC
VariantUndervoltage relay. Closed circuit operation
The voltage relay BA9036 of the VARIMETER series by Dold is an undervoltage relay for monitoring single-phase DC and AC voltage networks. It is used for continuous monitoring of operating voltage in industrial installations and prevents unwanted shutdowns or damage to connected devices by early detection of voltage drops or failures. The device setting is performed via rotary switches on the front, ensuring simple and user-friendly configuration. The device operates on the standby current principle, where the contacts are closed during normal operation and open in case of undervoltage. It is designed for use in enclosures and has a width of 45 mm, enabling compact mounting in standard control panels.

Applications
This relay is suitable for applications in industrial electrical engineering, particularly in installations requiring high operational reliability, such as in manufacturing automation, power supply, or building automation. It monitors voltages in the range of 24 to 400 V, with the nominal voltage for this variant being DC 127 V. The maximum nominal voltage is AC 400 V. The devices are specified according to IEC/EN 60255-1, ensuring high reliability and standard conformity. Monitoring is for single-phase systems, with setting ranges between 0.85 and 1.05 of the nominal voltage. For the variant /1_ _, the setting range is 0.9 to 1.25 of the nominal voltage.

Functions and Equipment in Detail
The relay features 2 changeover contacts as output contacts, which can be used for controlling auxiliary functions or alarms. The contacts are rated for a thermal current of 6 A and have a switching capacity according to AC 15 (make: 2 A / AC 230 V, break: 1 A / AC 230 V) and DC 13 (make: 1 A / DC 24 V, break: 1 A / DC 24 V). The electrical life is 150,000 switching operations at 6 A and AC 230 V, while the mechanical life is 30 million switching operations. The reset ratio (hysteresis) is between 0.75 and 0.95 of the set value, ensuring stable and reliable switching performance. The repeatability accuracy is ±0.5 %, enabling high precision in setting.

Technology Explained Simply
The device operates without auxiliary voltage, meaning it is directly connected to the voltage source to be monitored. The response delay is activated and can be set between 0.5 and 10 seconds, with the delay only effective when the voltage is above 60 % of the nominal voltage. This prevents unwanted switching operations during short-term voltage fluctuations. Operational readiness and contact status are indicated by LED displays: the upper LED lights up when operating voltage is present, and the lower LED lights up when the output relay is activated. For DC voltages above 60 V, an external resistor is required, connected to terminals e and z. For the DC 127 V variant, the resistor ZWS 20 SL 1.6 kΩ 20 W is specified.

Compatibility and Accessories
The relay is designed for use in enclosures and can be mounted in standard control panels. It is compatible with an external resistor required for DC voltages above 60 V. Accessories are listed in the datasheet under Accessories and Spare Parts, with the resistor ZWS 20 SL 1.6 kΩ 20 W specified for the DC 127 V variant. The devices are designed for operation in a temperature range of -20 °C to +60 °C, with identical specifications for operation and storage.

Mounting and Installation
Mounting is done in an enclosure, with the 45 mm width enabling standard mounting on DIN rails. Connections are made at terminals e, f, and z, with the measured voltage connected to e and f, and the external resistor connected to e and z. Terminal z is exclusively for the resistor. Mounting the resistor requires special caution, as it becomes very hot during operation and must be protected against contact and kept at sufficient distance from adjacent components.

Advantages in Operation
Early detection of voltage drops and preventive maintenance increase operational safety. The LED indicators enable quick fault localization, and the adjustable response and reset values allow application-specific adaptation. The high mechanical and electrical life, along with reliability according to IEC/EN 60255-1, make the relay a robust solution for industrial applications. Operational safety is further enhanced by the response delay and hysteresis, preventing unwanted switching operations during short-term disturbances.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter: