Further information for Dold 0028540 voltage relay BA9036 DC110V + RV D.FOLG.POS.
Technical data
1- / 3-phase
1
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
AC 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9036
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
DC 110 V
Time delay
without
Approvals and Markings
CCC
Variant
Undervoltage relay. Closed circuit operation
The voltage relay BA 9036 from Dold is an undervoltage relay for monitoring single-phase DC and AC power networks. It is designed for use in enclosures and has a width of 45 mm. The device operates on the principle of residual current and is rated for a nominal voltage of DC 110 V. The maximum nominal voltage is AC 400 V. Device settings are adjusted via rotary switches on the front panel, enabling simple and user-friendly configuration. The relay complies with IEC/EN 60255-1 standards and is intended for early detection of voltage drops to prevent failures in electrical systems and enhance operational safety.
Applications
The BA 9036 is designed for voltage monitoring in industrial and technical installations, particularly in systems requiring continuous power supply. It is suitable for applications in automation technology, power supply, and process control, where stable voltage is critical for smooth operation. Monitoring is performed for DC and AC voltages in the range of 24 to 400 V, with precise adjustment achieved via the rotary switch.
Functions and Features in Detail
The relay features two changeover contacts as output contacts, used for switching operations in control and protection circuits. The pickup delay is activated and can be set between 0.5 and 10 seconds, with the delay only effective when voltage exceeds 0.6 times the nominal voltage. The reset values are hysteresis-controlled and range between 0.75 and 0.95 of the set pickup value. Repeatability is ± 0.5 %, ensuring high precision in voltage monitoring. Operational readiness and contact status are indicated by LED displays: the upper LED lights up when operating voltage is present, and the lower LED indicates activation of the output relay.
Technical Explanation
The relay monitors the supply voltage and responds when it falls below a set threshold. In case of undervoltage, it switches the output contacts to, for example, activate a protective switch or trigger an alarm. Adjustment is made via a rotary switch, allowing pickup values between 0.85 and 1.05 times nominal voltage. For variant /1_ _, the adjustment range is 0.9 to 1.25 times nominal voltage. The pickup delay prevents unwanted switching during brief voltage fluctuations. Contacts are rated for a thermal current of 6 A and meet switching capacities according to AC 15 (make: 2 A / AC 230 V, break: 1 A / AC 230 V) and DC 13 (make: 1 A / DC 24 V, break: 1 A / DC 24 V). Electrical life is 150,000 switching operations at 6 A and AC 230 V, while mechanical life is 30 million switching operations.
Compatibility and Accessories
For DC 110 V operating voltage, an external resistor is required, connected to terminals e and z. The measured voltage is connected to terminals e and f. The resistor ZWS 20 SL with 1.5 kΩ and 20 W is intended for this purpose. Use of an external resistor is necessary because the voltage exceeds 60 V. Terminal z is exclusively for the resistor. The devices are operational without auxiliary voltage.
Mounting and Installation
The relay is designed for mounting in enclosures and conforms to the enclosure mounting form. Mounting is performed in a vertical position, with terminals accessible for connection wires. Operating and storage temperature ranges are between -20 °C and +60 °C. Maximum overload capacity is 1.2 times nominal voltage continuously. Nominal frequency is 50 or 60 Hz, with a frequency range of ±5 %. Temperature dependence of the measured value is < 0.05 %/K, indicating very low sensitivity.
Operational Advantages
Early detection of voltage drops enables preventive maintenance and reduces the likelihood of failures. LED indicators simplify diagnosis and fault localization. Simple adjustment via rotary switch reduces commissioning time. High contact life and robust construction ensure reliable performance over a long period. CCC certification confirms compliance with applicable safety standards.