Dold 0028259, EAN: 4030641282592

Dold 0028259 BA9036 AC50HZ 110V voltage relay

Dold 0028259 BA9036 AC50HZ 110V voltage relay

Lieske Part No. 1002182
Mfg Part No 0028259
EAN-Code 4030641282592
Manufacturer Dold
Here only 233,82 EUR
278,25 EUR incl. VAT

Further information for Dold 0028259 BA9036 AC50HZ 110V voltage relay

Technical data
1- / 3-phase1
Auxiliary voltageWithout
Enclosure designSwitch cabinet
Nominal voltage max.AC 400 V
Output contacts2 C/O contacts
Width45 mm
TypeBA 9036
Operate delayYes
Variant
Contact equipping2 changeover contacts
Nominal voltageAC 110 V 50 Hz
Time delaywithout
Approvals and MarkingsCCC
VariantUndervoltage relay. Closed circuit operation
The Dold voltage relay BA9036 AC50HZ 110V is an undervoltage relay of the VARIMETER series, designed for monitoring single-phase DC or AC power networks in industrial applications. It operates on the standby current principle and is intended for early detection of voltage drops to prevent failures in electrical systems. The device settings are adjusted via rotary switches on the front panel, enabling user-friendly and precise configuration of pickup and drop-out values. The device is designed for use in enclosures and complies with the standard IEC/EN 60255-1.

Applications
This relay is used in industrial plants where continuous voltage monitoring is required to ensure operational safety. It is suitable for applications where interruption of power supply could cause damage or downtime, for example in production plants, pump controls, or lighting systems. Monitoring is performed in the range of 24 to 400 V, with the rated voltage for this variant being AC 110 V at 50 Hz.

Functions and Equipment in Detail
The relay features 2 changeover contacts as output contacts, used for switching operations during operation. The contact configuration enables control of auxiliary functions or safety disconnections. Pickup delay is activated, preventing unwanted tripping due to short voltage fluctuations. Drop-out values are adjustable and range from 0.75 to 0.95 of the set pickup value, ensuring hysteresis. Repeatability is ±0.5 %, ensuring high precision in setting.

Technology Explained Simply
The device monitors the applied voltage and responds when it falls below the set pickup value. In case of undervoltage, the relay switches its output contacts, triggering for example an alarm or shutting down a machine. The LED indicators on the front panel signal operational readiness (upper LED) and active contact position (lower LED). Rated consumption values are 6 VA or 10 W, and the device is designed for continuous operation. Temperature dependence is < 0.05 %/K, ensuring stable performance even with temperature fluctuations.

Compatibility and Accessories
The relay is designed for use with a rated voltage of AC 110 V 50 Hz. The maximum rated voltage is AC 400 V. For DC voltages above 60 V, an external resistor is required, connected to terminals e and z. The measured voltage is connected to terminals e and f. Required resistors are available in the accessory range, for example ZWS 20 SL 1.5 kΩ 20 W for DC 110 V. Switching capacity is 2 A / AC 230 V for make contacts and 1 A / AC 230 V for break contacts according to AC 15, as well as 1 A / DC 24 V according to DC 13.

Mounting and Installation
The relay is intended for installation in enclosures and has a width of 45 mm. Mounting is done in standard control panels, with terminals provided for connection wires. The LED indicators allow visual monitoring of the operating status. When using an external resistor, sufficient shock protection and spacing from adjacent components must be ensured, as the resistor becomes very hot during operation.

Operational Advantages
By enabling early detection of voltage anomalies, the relay allows preventive maintenance and reduces the likelihood of machine downtime. Adjustable values and clear indication of contact position facilitate fault localization. The high mechanical life of 30 million switching operations and electrical life of 150,000 switching operations at 6 A / AC 230 V ensure long service life. Short-circuit resistance is secured with a maximum fuse rating of 4 A gG / gL.

Approvals and Markings
The device carries the CCC approval and meets the requirements of standard IEC/EN 60255-1. Operating temperature range is from -20 °C to +60 °C, with storage temperature also allowed between -20 °C and +60 °C. The device is operational without auxiliary voltage, simplifying installation and reducing dependency on additional power sources.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1002182
qrcode für Dold 0028259 BA9036 AC50HZ 110V voltage relay