Further information for Dold 0027056 BA9043/002 3/N AC50-400Hz 254/440V undervoltage relay 0.5-10s
Technical data
1- / 3-phase
3
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
3/N AC 690 / 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9043
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3/N 254/440 V
Time delay
0,5 - 10 s
Approvals and Markings
UKCA
Variant
For 3p4w systems. With adjustable time delay
The under-voltage relay BA9043/002 from Dold is a 3-phase monitoring device for AC networks with neutral conductor. It is designed for continuous monitoring of the network voltage and de-energizes output contacts in case of under-voltage, protecting connected devices from damage. The device is rated for nominal voltages of 3/N AC 254/440 V and can be used in networks with frequencies from 50 to 400 Hz. Measurement is performed via arithmetic mean value calculation, with each phase measured against the neutral conductor. Device settings are adjusted via rotary potentiometers on the front panel, allowing the pickup and dropout values to be continuously adjusted between 0.85 and 1.05 of the nominal voltage, and the hysteresis between 0.75 and 0.95 of the pickup value.
Applications
This relay is suitable for industrial applications as well as railway applications. It monitors 3-phase AC networks and is particularly intended for systems requiring high availability. The operating temperature ranges from -20 °C to +60 °C, making it suitable for use in demanding climatic environments.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, designed for switching operations with a thermal current of up to 6 A per contact. Switching capacities are 2 A / AC 230 V for closing contacts and 1 A / AC 230 V for opening contacts according to AC 15 (IEC/EN 60947-5-1). The electrical life expectancy is at least 200,000 switching operations at 3 A and AC 230 V. The mechanical life expectancy exceeds 30 million switching operations. LED indicators signal operational readiness (red LED) and activation of the output relay (green LED). The fail-safe principle ensures that the output relay is not activated in case of fault, increasing safety.
Technology Explained Simply
The time delay is adjustable and ranges from 0.5 to 10 seconds. However, it only applies if the voltage is at least 60 % of the nominal voltage. Below 40 % of the nominal voltage, the output relay drops out immediately. Adjustment is made via a rotary potentiometer on the front panel. The devices comply with IEC/EN 60255-1 and are designed for use in enclosures. The width is 45 mm, allowing mounting on DIN rail. The devices are insensitive to harmonics, making them suitable for networks with non-linear loads.
Compatibility and Accessories
The relay is available for networks with or without neutral conductor, with the BA9043/002 variant specifically designed for systems with neutral conductor. The adjustable time delay makes it suitable for applications with short-term voltage dips. The devices are designed for frequencies from 50 to 400 Hz, which is also relevant for railway applications. The devices are designed for use in overvoltage category III and have a rated impulse withstand voltage of 6 kV at pollution degree 2.
Mounting and Installation
Mounting is on DIN rail according to IEC/EN 60715. The terminal connections are rated for 2 x 2.5 mm² solid or 2 x 1.5 mm² stranded zinc-coated cable. Cable fixation is achieved via M3.5 plus-minus screws with self-releasing clamp lever. Dimensions are 45 mm (width) x 73 mm (height) x 132 mm (depth). Mounting requires no additional auxiliary voltage, as the device is directly powered from the monitored network.
Advantages in Operation
Preventive maintenance is supported by rapid fault localization. The LED indicators enable visual monitoring of the operational status. The adjustable pickup and dropout values, as well as the time delay, allow application-specific adaptation. Harmonic insensitivity ensures stable operation even in networks with non-linear loads. The construction according to IEC/EN 60255-1 ensures high reliability and safety.
Approvals and Markings
The device carries the UKCA mark, confirming compliance with applicable European safety and performance requirements. The devices are intended for use in industrial and railway applications and meet the requirements of overvoltage category III. EMC requirements are fulfilled according to IEC/EN 61000-4-2 to -4-5, including protection against electrostatic discharge (8 kV), high-frequency radiation (20 V/m), and fast transients (2 kV).