| Technical data |
| Classification | Thermistor-Motorschutz |
| Enclosure design | Switch cabinet |
| Measuring range max. | > 3 kΩ |
| Output contacts | 2 C/O contacts |
| Width | 22,5 mm |
| Type | MK 9052 |
| Variant |
| Auxiliary voltage | AC 24 V |
| Contact equipping | 2 changeover contacts |
The Dold MK9052.12 AC50/60HZ 24V is a
thermistor motor protection relay for use in industrial enclosures. It prevents thermal motor overloads caused by high switching frequency, heavy start-up, single-phase operation, impaired cooling, or high ambient temperature. The device monitors the temperature of electric motors via special thermistors (PTC resistors) and switches off the motor when a critical resistance value is reached. The auxiliary voltage is AC 24 V, and the relay is equipped with
2 changeover contacts, enabling flexible integration into existing circuits. The width of 22.5 mm allows compact mounting on a DIN rail within the enclosure.
Applications
The motor protection relay MK9052.12 is designed for use in industrial plants where reliable monitoring of motor heat is required. It is particularly used in drive technology, pumps, fans, conveyor systems, and other machinery where thermal overload protection is necessary. The application is intended for environments with an operating temperature of -20 °C to +60 °C and an operating altitude below 2000 m. The protection rating IP 40 for the housing and IP 20 for the terminals ensures sufficient protection against contact and foreign objects, but not against splashing water or dust – thus it is intended for indoor use.
Functions and Equipment in Detail
The relay operates on the
standby current principle, where the output relay is not activated in the event of a fault. This means the motor is only switched off when the temperature sensor (thermistor) reaches a resistance of at least 3 kΩ – a value indicating critical heating. The reset value is at most 1.8 kΩ, so the relay reactivates after the motor has cooled down. The
wire break detection in the sensor circuit ensures that a broken sensor wire is also recognized as a fault. Up to six thermistors can be connected in series to ensure comprehensive temperature monitoring. An LED indicates the relay’s switching state.
Technology Explained Simply
The input voltage for the temperature sensor is approximately 1.2 V at a resistance of 1.5 kΩ, with a measurement circuit load of about 1 mW. The auxiliary voltage of AC 24 V is supplied via terminals A1/A2. The relay has a rated consumption of 1.8 VA at a frequency of 50/60 Hz. The response delay is less than 20 ms, and the reset delay is less than 15 ms, enabling a rapid reaction to temperature changes. The contact configuration with 2 changeover contacts allows control of multiple circuits. The mechanical life exceeds 20 million switching operations, and the electrical life is 800,000 switching operations at 3 A and AC 230 V.
Compatibility and Accessories
The device is compliant with IEC/EN 60947-8 and can be operated with thermistors or bimetal contacts. The terminals are designed for conductor cross-sections of 2 x 2.5 mm² (solid) or 2 x 1.5 mm² (stranded wire with ferrule DIN 46228-1/-2/-3/-4). Mounting is done on a DIN rail (IEC/EN 60715). The switching capacity is 3 A/AC 230 V for make contacts and 1 A/AC 230 V for break contacts. The maximum fuse rating is 4 A gG/gL. The EMC characteristics comply with standards IEC/EN 61000-4-2 to -4-6, including radio frequency interference suppression according to EN 55011, Class B.
Mounting and Installation
Mounting is done on a DIN rail within the enclosure. The connection terminals are clearly labeled: A1/A2 for operating voltage, P1/P2 for thermistor input, and the changeover contacts are marked as 11/12/14 and 21/22/24. The tightening torque is 0.4 Nm. Vibration resistance is ensured according to IEC/EN 60068-2-6 with an amplitude of 0.35 mm and a frequency of 10 to 55 Hz. Climate resistance corresponds to designation 20/060/04 according to IEC/EN 60068-1.
Advantages in Operation
The MK9052.12 provides reliable, low-maintenance monitoring of motor heat. The integrated wire break detection prevents malfunctions due to defective sensors. The clear indication via LED simplifies diagnosis. The compact design and DIN rail mounting enable flexible integration into existing control systems. The high mechanical and electrical life ensures long-term operation without replacement. Compliance with IEC/EN 60947-8 and EMC testing according to IEC/EN 61000-4-2 to -4-6 guarantee safe and interference-free operation in industrial environments.