Further information for Dold 0012928 IK8800.12DC24V surge switch
Technical data
Output contacts max.
4 C/O contacts
Thermal current Ith
16 A
Width
17,5 mm
Type
IK 8800
For top hat rail mounting
Variant
Contact equipping
2 changeover contacts
Nominal voltage
DC 24 V
The product is a pulse-operated switch of the IK 8800 series by Dold, type IK8800.12DC24V, specifically designed for use in electrical installations. It is a modular device with impulse operation, which activates the output contacts with each current pulse and holds them in the respective switching position until the next pulse. The contact configuration includes 2 changeover contacts, with the series also offering variants with up to 4 changeover contacts. The rated voltage is DC 24 V, making it suitable for applications in direct current systems. The device is designed for mounting on a DIN rail and has a width of 17.5 mm, enabling compact placement in enclosures. The maximum thermal current rating (Ith) is 16 A, defining the electrical load capacity of the device.
Applications
The IK8800.12DC24V is typically used in installations where multiple room switches or remote switches are connected to a central switching device. The impulse operation minimizes energy consumption, as the device only draws power during actuation. Mounting in rows is possible, with devices able to be placed closely together during impulse operation. For continuous switching, a mounting distance of 7 mm between relays is required to ensure heat dissipation and thermal load management.
Functions and Equipment in Detail
The device features a manual actuation button for the contacts, allowing the switching position to be changed without an electrical impulse. The current switching position is indicated by a visual indicator, which visually signals the state of the contacts, facilitating maintenance and diagnostics during operation. The contact position is indicated by a red visual indicator when the output contacts are activated. Actuation is performed via a control signal at terminals A1 (L/DC+) and A2 (N/DC-), with the output contacts (13/14, 23/24) controlling the load circuit.
Technology Explained Simply
The impulse operation means the device only consumes power when a pulse is applied via the control signal at A1/A2. The contacts remain in the position they have assumed until the next pulse arrives. This reduces energy consumption and wiring effort, especially in installations with multiple room switches, as only one control signal per device is required. The switching time is less than 30 ms, ensuring a rapid response. The electrical life at resistive load (AC 230 V) is up to 150,000 switching cycles at 6 A and up to 10,000 switching cycles at 16 A. The mechanical life is 3 million switching cycles.
Compatibility and Accessories
The device is compliant with IEC/EN 60669 and can be used in systems meeting this standard. It is intended for use in enclosures with DIN rail mounting. The width of 17.5 mm allows for compact arrangement. The IK 8800 series offers various contact configurations, with the IK8800.12DC24V variant equipped with 2 changeover contacts. Other variants with 1, 3, or 4 changeover contacts are also available, but are not part of this specific item.
Mounting and Installation
Mounting is performed on a standard DIN rail. During impulse operation, devices can be mounted closely together. For continuous switching, a spacing of 7 mm between relays is required to avoid thermal stress. The operating temperature range is from -20 °C to +45 °C, and the storage temperature range is from -25 °C to +55 °C. The maximum permissible altitude is 2000 m above sea level.
Operational Advantages
The impulse operation results in low energy consumption, as the device only draws power during actuation, reducing the load on the power supply and lowering consumption. The reduced wiring effort in installations with multiple room switches is achieved through centralized control via a single control signal. The manual actuation and visual indication of switching position simplify maintenance and fault diagnosis. Compliance with IEC/EN 60669 ensures reliability and safety in use.