ABB 2CSR275189R1255, EAN: 8012542595519

ABB Automation 2CSR275189R1255 residual current circuit breaker 1P+N B25 30mA

Installation > Modular devices / equipment installation > RCD

ABB Automation 2CSR275189R1255 residual current circuit breaker 1P+N B25 30mA

Lieske Part No. 665434
Mfg Part No 2CSR275189R1255
EAN-Code 8012542595519
Manufacturer ABB
Here only 172,90 EUR
205,75 EUR incl. VAT

Further information for ABB Automation 2CSR275189R1255 residual current circuit breaker 1P+N B25 30mA

General
Number of poles (total)2
Number of protected poles1
Rated voltage240
Rated insulation voltage Ui500
Rated impulse withstand voltage Uimp4
Rated current25
Rated fault current0.03
Leakage current typeA
Current limiting class3
Rated short-circuit breaking capacity acc. EN 6100910
Rated short-circuit breaking capacity IEC 60947-215
Rated short-circuit breaking capacity Icn acc. EN 61009-110
Disconnection characteristicUndelayed
Voltage typeAC
FrequencyOther
Release characteristicB
Over voltage category3
Pollution degree2
Ambient temperature during operating55
Width in number of modular spacings2
Built-in depth69
Degree of protection (IP)IP20
Connectable conductor cross section multi-wired16
Mounting methodDIN rail
Power loss8.1
Concurrently switching N-neutralyes
With interlocking deviceno
Anti-nuisance tripping versionno
The ABB FI/LS switch type DS201 M B25 A30 110V is a combined residual current and load switch (RCBO), designed for use in single-phase circuits in commercial and industrial applications. It provides protection against overload, short-circuit currents, and fault currents, particularly for sinusoidal alternating currents and pulsating currents with a smooth direct fault current component up to 6 mA. The switch complies with product standards IEC 61009-1 and IEC 61009-2-1 and is specifically designed for applications with an operating voltage of 110 V AC to 230 V AC. The DS201 MA 110V series does not have VDE approval, but features international approvals such as CCC (CN), ABS (USA), DNV (DE), RINA (IT), RMRS (RU), and Lloyd's Register (GB). It is suitable for use in electrical installations according to DIN VDE 0100-410 and DIN VDE 0100-530, ensuring personal, property, and fire protection.

Applications

The switch is primarily intended for use in commercial and industrial installations where combined protection against electrical hazards is required. It protects against indirect contact (fault protection) and provides additional protection against fires caused by electrical faults. The application is in single-phase circuits, with an operating voltage ranging from 110 V AC to 230 V AC. The protection functions are designed for installations operating in environments with an ambient temperature up to 55 °C.

Functions and Equipment in Detail

The FI/LS switch is protected on 1 pole (LS) and switching on 2 poles, with the neutral conductor switching simultaneously. The rated voltage is 240 V, and the rated insulation voltage Ui is 500 V. The rated current is 25 A, and the rated residual current is 30 mA. The residual current type is A, meaning it can also detect pulsating fault currents with a direct current component. The tripping characteristic is instantaneous, and the release characteristic corresponds to type B, suitable for typical consumer loads. The energy limitation class is 3, ensuring limited energy release during switching off.

Technology Explained Simply

The switch combines the functions of a load switch (LS) and a residual current switch (FI) in one device. It disconnects the circuit when the current exceeds the rated current (25 A) (overload protection) or when a short circuit occurs. Additionally, it detects fault currents from 30 mA, indicating insulation damage or contact to earth. The rated breaking capacity is 10 kA according to EN 61009 and 15 kA according to IEC 60947-2, with the rated short-circuit making capacity Icn according to EN 61009-1 also being 10 kA. The protection class IP20 protects against finger contact and solid foreign objects, but not against water or dust. The overvoltage category 3 and pollution degree 2 indicate an operating environment where moderate overvoltages and low pollution levels may occur.

Compatibility and Accessories

Various accessories are available for this switch, extending its functionality. These include the Si-automat S200 B+ LS S2C-H6-20R, which can function as an additional load switch, as well as auxiliary switches such as the S2C-S/H6R (1 changeover contact) and the LS S2C-H6-11R. These components enable expansion of control and monitoring functions in complex installations. Mounting is on a DIN rail, with an installation depth of 69 mm and a width of 2 module units. The maximum cross-section for stranded conductors is 16 mm².

Mounting and Installation

The switch is mounted on a DIN rail, enabling standardized and secure installation in enclosures. The installation depth of 69 mm must be considered when planning the enclosure depth. The power dissipation is 8.1 W, which is relevant for thermal planning of the enclosure environment. Mounting is done without additional interlocking devices, simplifying installation, although it does not allow for mechanical interlocking between switches.

Advantages in Operation

The combined protection provided by the FI/LS switch reduces the number of devices required in enclosure planning and lowers installation costs. The instantaneous tripping at fault currents increases operational safety. The type A detection enables use in installations with electronic devices that generate pulsating fault currents. The approvals from various countries facilitate use in international projects. The rated switching capacity of 10 kA (IEC/EN 61009) is sufficient for typical industrial applications.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/665434
qrcode für ABB Automation 2CSR275189R1255 residual current circuit breaker 1P+N B25 30mA