| General |
| Nominal voltage | 300/500 V |
| Test voltage | 2000 V |
| Operation temperature | +70 °C |
| Installation temperature range | +5 to +60 °C |
| Temperature range after installation | -20 to +70 °C |
| Bending radius | 4 x cable diameter |
| Conductor | Bare copper according to VDE 0295 |
| Wire insulation | Cross-linked polyethylene mixture |
| Conductor marking | according to VDE 0293-308 |
| Filler compound | Halogen-free and flame retardant |
| Outer sheath | Halogen-free polymer blend, flame retardant |
| Sheath colour | Grey RAL 7001 |
| Burning behaviour | according to VDE 0472 T. 804, test type C (IEC 332-1) |
| Corrosivity of fire gases | according to VDE 0472 T. 813 |
| Flue gas density | according to VDE 0472 T. 816, test type C (IEC 1034-1) |
| Halogen-free | According to VDE 0472 Part 815 |
| Ozone resistance | According to VDE 0472 T. 805 |
| Flame retardancy | VDE 0482-266-2-4, IEC 60332-3-24 |
The
halogen-free cable NHXMH-J 12x1.5 from Xaver Bechtold is a
sheathed cable designed for use in buildings with high personnel and/or asset concentration. It is suitable for installation over, on, in, and under plaster, in dry, damp, and wet rooms, as well as in masonry and concrete. Direct embedding in vibrated, compacted, or rammed concrete is excluded. The cable is also suitable for outdoor use, making it particularly appropriate for outdoor installations and industrial applications with increased safety requirements.
Applications
The cable is designed for use in residential and commercial buildings, office buildings, hospitals, schools, and other facilities with high visitor traffic. It is frequently used in electrical installations where minimizing smoke development and avoiding toxic gases in the event of fire are critical. Installation in masonry or concrete enables flexible integration into existing or new building structures.
Functions and Equipment in Detail
The
halogen-free cable consists of copper conductors in accordance with VDE 0295, which are either solid round or stranded. The core insulation is made of a cross-linked polyethylene mixture, providing high mechanical and thermal resistance. Core identification follows VDE 0293-308, ensuring clear identification of individual cores. A halogen-free and flame-retardant filler sheath provides additional stability and protection for the cores. The outer sheath is made of a halogen-free polymer mixture, also flame-retardant, protecting the cable from external influences. The sheath color is gray, corresponding to RAL 7001.
Technology Explained Simply
The
rated voltage is 300/500 V, indicating the maximum voltage at which the cable can be safely operated. The
test voltage of 2000 V is used for quality testing to ensure the insulation does not break down under increased voltage. The
operating temperature is limited to a maximum of +70 °C. During installation, the cable can withstand temperatures from +5 °C to +60 °C. After installation, it can operate in temperatures from -20 °C to +70 °C. The
minimum bending radius is 4 times the cable diameter, allowing safe bending without damaging the cores.
Compatibility and Accessories
The cable is designed for use in electrical installations operating at 300/500 V. It is compatible with other
halogen-free cables of type NHMH or NHXMH, especially in installations requiring high safety standards regarding fire behavior and smoke development. Use in combination with appropriate connection elements, such as terminals or connectors, is possible, provided they meet the same electrical and mechanical requirements.
Installation and Mounting
Installation is carried out by laying over, on, in, and under plaster, in masonry, or concrete. The cable must not be embedded in vibrated, compacted, or rammed concrete. Outdoor installation is permitted, taking into account environmental conditions such as temperature and humidity. Bending the cable must comply with the specified minimum bending radius of 4 times the cable diameter to avoid core damage.
Operational Advantages
The
halogen-free cable significantly reduces smoke development in the event of fire and helps prevent fire spread. No corrosive or toxic gases are released, increasing personnel safety and protecting electronic equipment. The flame-retardant properties of the insulation and outer sheath contribute to fire resistance. High ozone resistance and resistance to mechanical stress increase the cable’s service life. Use in buildings with high personnel and asset concentration is particularly advantageous due to these safety features.
Testing and Standards
The cable meets fire behavior requirements according to VDE 0472 T. 804 (Test Method C, equivalent to IEC 332-1). Corrosivity of combustion gases is tested according to VDE 0472 T. 813, and smoke gas density according to VDE 0472 T. 816 (Test Method C, equivalent to IEC 1034-1). Halogen-free status is verified according to VDE 0472 T. 815. Ozone resistance is tested according to VDE 0472 T. 805. Flame retardancy complies with standards VDE 0482-266-2-4 and IEC 60332-3-24.