General
Nominal voltage300/500 V
Test voltage2000 V
Installation temperature range+5 °C - +60 °C
Temperature range after installation-20 °C - +70 °C
Operation temperature+70 °C
Bending radius4 x cable diameter (min.)
ConductorBare copper according to VDE 0295
Wire insulationCross-linked polyethylene mixture
Conductor markingaccording to VDE 0293-308
Filler compoundHalogen-free and flame retardant
Outer sheathHalogen-free and flame-retardant polymer blend
Sheath colourGrey RAL 7001
Burning behaviourAccording to VDE 0472 T. 804, test type C (=IEC 332-1)
Corrosivity of fire gasesaccording to VDE 0472 T. 813
Flue gas densityaccording to VDE 0472 T. 816, test type C (=IEC 1034-1)
Halogen-freeAccording to VDE 0472 Part 815
Ozone resistanceAccording to VDE 0472 T. 805
Flame retardancyVDE 0482-266-2-4, IEC 60332-3-24
The NHXMH-J 5x6 cable from Xaver Bechtold is a halogen-free sheathed cable designed for use in buildings with high personnel and/or asset concentration. It is suitable for installation over, on, in, and under plaster, in dry, damp, and wet rooms, as well as in masonry and concrete. Direct embedding in vibrated, compacted, or rammed concrete is excluded. The cable is also suitable for outdoor use. Due to its halogen-free composition, it exhibits minimal smoke development and does not release corrosive or toxic gases when exposed to flame. It also prevents the spread of fire, making it particularly suitable for safety-critical applications.

Applications
This cable is intended for use in residential and commercial buildings, office buildings, hospitals, schools, and other facilities with high visitor traffic or valuable equipment. Installation can take place both indoors and outdoors, with the cable also being suitable for use in damp and wet rooms as well as in concrete structures. Outdoor use is possible, as the cable exhibits high weather resistance.

Functions and Features in Detail
The cable consists of copper conductors in accordance with VDE 0295, which are either solid round or stranded. The core insulation is made of cross-linked polyethylene mixture, providing high mechanical and thermal resistance. Core identification follows VDE 0293-308, enabling clear identification of individual cores. The filler and outer sheath are halogen-free and flame-retardant, minimizing fire load. The outer sheath is grey RAL 7001, ensuring good visibility while remaining unobtrusive.

Technical Explanation
The rated voltage is 300/500 V, sufficient for most electrical installations in buildings. The test voltage of 2000 V ensures the electrical strength of the insulation. The maximum operating temperature is +70 °C, with installation temperatures ranging from +5 °C to +60 °C. After installation, the cable can withstand temperatures from -20 °C to +70 °C. The minimum bending radius is 4 times the cable diameter, allowing flexible installation. The cable meets flame retardancy requirements according to VDE 0482-266-2-4 and IEC 60332-3-24, meaning it does not burn independently and does not propagate flame when exposed to fire. Ozone resistance in accordance with VDE 0472 T. 805 ensures long service life even in environments with elevated ozone levels.

Compatibility and Accessories
The cable is designed for use in electrical installations requiring halogen-free and flame-retardant cabling. It can be combined with appropriate connection components, such as sockets, switches, and distributors, which also meet safety and fire behaviour requirements. Use in combination with other halogen-free cables is possible to ensure consistent safety levels throughout the building.

Installation and Mounting
Installation must consider the specified temperature ranges. During installation, temperatures must be between +5 °C and +60 °C; after installation, the cable can withstand temperatures from -20 °C to +70 °C. The minimum bending radius of 4 times the cable diameter must be maintained to ensure mechanical integrity. The cable is suitable for installation in concrete structures, but not for direct embedding in vibrated, compacted, or rammed concrete. Installation is typically performed by electricians complying with electrical regulations (e.g. VDE 0100).

Operational Advantages
The halogen-free composition of the cable significantly reduces fire hazard and the consequences of a fire. Minimal smoke development and the absence of toxic gases increase safety for people in the building. The flame-retardant property prevents flame propagation along the cable, facilitating fire fighting. High mechanical and thermal resistance ensures long service life and low maintenance costs. Outdoor and damp room use expands the application range and reduces the need for additional protective measures.