| General |
| Nominal voltage | 300/500 V |
| Test voltage | 2000 V |
| Operation temperature | +70 °C |
| Installation temperature range | +5 to +60 °C |
| Temperature range after installation | -20 to +70 °C |
| Bending radius | 4 x cable diameter min. |
| Wire insulation | Cross-linked polyethylene mixture - |
| Conductor marking | according to VDE 0293-308 - |
| Filler compound | Halogen-free and flame retardant - |
| Outer sheath | Halogen-free and flame-retardant polymer blend - |
| Sheath colour | Grey RAL 7001 - |
| Burning behaviour | According to VDE 0472 T. 804, test type C (=IEC 332-1) - |
| Corrosivity of fire gases | according to VDE 0472 T. 813 - |
| Flue gas density | according to VDE 0472 T. 816, test type C (=IEC 1034-1) - |
| Halogen-free | According to VDE 0472 Part 815 - |
| Ozone resistance | According to VDE 0472 T. 805 - |
| Flame retardancy | VDE 0482-266-2-4, IEC 60332-3-24 - |
The NHXMH-J 1X16 cable from Xaver Bechtold is a halogen-free sheathed cable designed for use in buildings with high personnel and/or asset concentration. It is suitable for installation over, on, in, and under plaster, in dry, damp, and wet rooms, as well as in masonry and concrete. Direct embedding in vibrated, compacted, or rammed concrete is excluded. The cable is also suitable for outdoor use. Due to its halogen-free composition, it features minimal smoke development and does not release corrosive or toxic gases when exposed to flame. It prevents fire spread and is therefore particularly suitable for applications in sensitive areas.
Applications
This cable is intended for use in residential and commercial buildings, office buildings, hospitals, schools, and other facilities with high visitor traffic or valuable equipment. It can be installed both indoors and outdoors, with concrete installation subject to the specified restrictions. Outdoor use is possible due to weather-resistant materials, although direct embedding in wet or moving concrete masses is not permitted.
Functions and Features in Detail
The cable consists of a copper conductor in accordance with VDE 0295, which is either round single-strand or multi-strand. The core insulation is made of cross-linked polyethylene mixture, ensuring high electrical insulation. Core identification follows VDE 0293-308, enabling clear identification of conductors. The filler sheath and outer sheath are halogen-free and flame-retardant. The outer sheath is made of a polymer mixture and is grey in colour, RAL 7001, ensuring good visibility while remaining unobtrusive in installations.
Technical Details Explained
The rated voltage is 300/500 V, making the cable suitable for use in standard AC networks. The test voltage of 2000 V ensures electrical strength. The maximum operating temperature is +70 °C, with installation temperatures ranging from +5 °C to +60 °C. After installation, the cable can withstand temperatures from -20 °C to +70 °C. The minimum bending radius is 4 times the cable diameter, allowing flexible installation without compromising mechanical integrity. Flame retardancy according to VDE 0482-266-2-4 and IEC 60332-3-24, along with smoke density testing according to VDE 0472 T. 816 (test type C = IEC 1034-1), ensures high safety in case of fire. Ozone resistance according to VDE 0472 T. 805 protects the cable from aging due to ozone exposure.
Compatibility and Accessories
The cable is designed for use in electrical installations requiring halogen-free and flame-retardant cabling. It can be combined with other NHXMH or NHMH cables, provided technical requirements such as voltage, cross-section, and temperature range are compatible. Use in combination with suitable cable protection conduits, cable trays, or other installation components is possible, as long as mechanical and thermal loads are not exceeded.
Installation and Mounting
Installation must consider the specified temperature ranges. During installation, temperatures must be between +5 °C and +60 °C. After installation, the cable can be exposed to temperatures from -20 °C to +70 °C. The bending radius must be at least 4 times the cable diameter. The cable must not be embedded in vibrated, compacted, or rammed concrete. Installation follows standard techniques for sheathed cables, including the use of cable ties, cable protection conduits, or cable ducts, provided they meet the requirements of applicable standards.
Operational Advantages
The halogen-free composition reduces smoke development in case of fire and prevents the release of toxic or corrosive gases. The flame-retardant property slows flame spread and increases building safety. High electrical strength and resistance to ozone ensure long service life and reliable performance. Outdoor use is possible, increasing application flexibility. The grey colour RAL 7001 provides good visibility while remaining unobtrusive in installations.