VOKA

VOKA A-2Y(L)2Y 2x2x0,8 Telephone Cable Underground

Cables > Underground cables > Telecommunications underground cable

VOKA A-2Y(L)2Y 2x2x0,8 Telephone Cable Underground

Lieske Part No. 162914
Mfg Part No
EAN-Code
Manufacturer VOKA
Here only 1,56 EUR
1,86 EUR incl. VAT

Further information for VOKA A-2Y(L)2Y 2x2x0,8 Telephone Cable Underground

General
Conductor diameter0,8 mm
Wire insulationPE -
Nominal voltage225 V
Test voltage2000 V
Loop resistance73,2 Ohm/km
Current carrying capacity5,1 A
Operating capacity55 nF/km
Insulation resistance5 GOhm x km
Capacitive couplings K3300 pF/400 pF at 800 Hz, 300 m
Line attenuation0,78 dB/km
Installation temperature range-20 °C to +50 °C -
Temperature range after installation-30 °C to +70 °C -
Bending radius7.5 x cable diameter -
Material outer sheathaluminium tape with plastic coating and PE sheath -
Conductor markingblack rings -
Sheath markingTelephone handset, white meter marking -
The VOKA telecommunication underground cable type A-2Y(L)2Y 2 X 2 X 0,8 is a specialised cable for underground installation in the field of telephony and data transmission. It is primarily used in outdoor installations, especially as local access or local connection cables, in railway station telecommunication systems, and in industrial facilities. The cable is designed for low-frequency transmission purposes and is typically operated unspooled in the trunk network. It complies with DIN VDE 0816 Part 1 standards and is approved for use in operational sites, with special restrictions applying to mine workers according to DIN VDE 0118. Cables with an outer PE sheath are not permitted in fire- or explosion-hazardous areas without additional protective measures. Use for high-voltage installation purposes is expressly excluded.

Applications
This cable is designed for underground installation and is suitable for use in outdoor environments where a robust and long-lasting connection is required. It is frequently used in telecommunications, for example, for connecting local networks or as part of railway station telecommunication cables. The construction with polyethylene (PE) as insulation and sheathing material ensures high mechanical and chemical resistance. Installation must consider the specified temperature ranges: laying between -20 °C and +50 °C, and operation after laying between -30 °C and +70 °C.

Functions and Equipment in Detail
The cable consists of single-strand, bare copper conductors with a diameter of 0.8 mm. The conductors are insulated with PE (2Y) and marked with black rings to enable easy identification. The stranding is done in a star quad system: four conductors form a star quad, five star quads form a basic bundle, and five or ten basic bundles form a main bundle. These bundles are stranded into a cable core, which is additionally wrapped with a core wrapping. The outer sheath consists of a layered sheath made of a 0.2 mm thick aluminium tape coated on both sides with plastic, and fused with a black PE sheath. The sheath marking is continuous with the inscription “Fernsprech-Handapparat” and white metre markings, facilitating precise length determination and positioning.

Technology Explained Simply
The technical properties of the cable are tailored to the requirements of telecommunication and data transmission. The rated voltage is 225 V, and the test voltage is 2000 V, ensuring high electrical strength. The loop resistance is 73.2 Ohm/km, ensuring efficient signal transmission. The current-carrying capacity is 5.1 A, sufficient for typical loads in telecommunication systems. The operating capacitance is 55 nF/km, and the insulation resistance is 5 GOhm x km, indicating high insulation quality and low leakage currents. The capacitive couplings (K3) are 300 pF/400 pF at 800 Hz and a length of 300 m, affecting signal quality. The line attenuation is approximately 0.78 dB/km at 800 Hz, indicating low signal attenuation over length. The bending radius is 7.5 times the cable diameter, enabling flexible installation.

Compatibility and Accessories
The cable is designed for use in telecommunication systems and can be combined with other cables of the same type or compatible systems. It is designed for underground installation and does not require additional protective measures when installed in non-hazardous areas. Installation must comply with VDE standards, particularly DIN VDE 0816 Part 1.

Installation and Mounting
Installation is carried out by underground laying, observing the specified temperature ranges and bending radius (7.5 times the cable diameter). The cable is laid in an appropriate trench, with the cable core protected mechanically by stranding and the layered sheath. The sheath marking facilitates length measurement and positioning. After installation, the cable must be operated in the intended environment, ensuring that temperature limits of -30 °C to +70 °C are not exceeded.

Operational Advantages
The cable offers high mechanical stability and electrical reliability. The PE insulation and layered sheath provide high resistance to environmental influences. The low line attenuation and high insulation resistance ensure stable signal transmission. Clear marking of conductors and sheath simplifies installation and maintenance. Use in telecommunication systems enables reliable and long-term operation without additional protective measures in non-hazardous areas.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/162914
qrcode für VOKA A-2Y(L)2Y 2x2x0,8 Telephone Cable Underground