SM 031 - Analog input
4x AI
16 Bit
Resistance 0.3000 Ohm
Resistance measurement 2-, 3-, and 4-wires
Resistance temperature transmitter Pt100, Pt1000, NI100 and NI1000
Reduced parameter bytes
SM 031 - Analog Input (031-1LD80)
Technical Data:
Order No.:
Type:
Module ID:
General Information:
- Note: -
- Features: 4x AI, 16 Bit, Resistance 0…3000 Ohm, Resistance measurement 2-, 3-, and 4-wire, Resistance temperature transmitter Pt100, Pt1000, Ni100, Ni1000, Reduced parameter bytes
Current Consumption/Power Loss:
- Current consumption from backplane bus: 55 mA
- Power loss: 1 W
Technical Data Analog Inputs:
- Number of inputs: 4
- Cable length, shielded: 200 m
- Rated load voltage: DC 24 V
- Current consumption from load voltage L+ (without load): 30 mA
- Voltage inputs: -
- Min. input resistance (voltage range): -
- Input voltage ranges: -
- Operational limit of voltage ranges: -
- Operational limit of voltage ranges with SFU: -
- Basic error limit voltage ranges: -
- Basic error limit voltage ranges with SFU: -
- Destruction limit voltage: -
- Current inputs: -
- Max. input resistance (current range): -
- Input current ranges: -
- Operational limit of current ranges: -
- Operational limit of current ranges with SFU: -
- Basic error limit current ranges: -
- Radical error limit current ranges with SFU: -
- Destruction limit current inputs (voltage): -
- Destruction limit current inputs (electrical current): -
- Resistance inputs: yes
- Resistance ranges: 0 ... 60 Ohm, 0 ... 600 Ohm, 0 ... 3000 Ohm
- Operational limit of resistor ranges: +/- 0.4 %
- Operational limit of resistor ranges with SFU: +/- 0.2 %
- Basic error limit: +/- 0.2 %
- Basic error limit with SFU: +/- 0.1 %
- Destruction limit resistance inputs: max. 24 V
- Resistance thermometer inputs: yes
- Resistance thermometer ranges: Pt100, Pt1000, Ni100, Ni120, Ni1000
- Operational limit of resistance thermometer ranges: +/- 0.4 %
- Operational limit of resistance thermometer ranges with SFU: +/- 0.2 %
- Basic error limit resistance thermometer ranges: +/- 0.2 %
- Basic error limit resistance thermometer ranges with SFU: +/- 0.1 %
- Destruction limit resistance thermometer inputs: max. 24 V
- Thermocouple inputs: -
- Thermocouple ranges: -
-