Further information for VDE-Kabel NHXCH-E90 4 X 10,0/ 10,0 (G446096)
'Halogen-free cable with insulation and
functional integrity NHXCH FE 180 E90
Application:
Safety cables are used wherever special protection
against fire and fire damage to people and property
is necessary and long emergency running times must be met, such as in
airports, hospitals and schools . Can be used indoors and outdoors
, but should not be laid directly in soil or water. The formation of smoke caused by
fire, which makes escape routes impossible to find
and causes the development of toxic gases, is prevented.
Insulation retention of at least 180 minutes and functional retention of
at least 90 minutes. Safety for over 90 minutes guarantees the functionality
of water pressure boosting systems for extinguishing water supply,
ventilation systems, smoke and heat exhaust systems and fire brigade
lifts, etc.
Construction:
Conductor: bare copper conductor according to VDE 0295,
round single-wire or multi-wire
50 mm2 are compressed
mica tape
Core insulation: polymer mixture halogen-free
according to VDE 0207 T. 23
Core identification: according to VDE 0293
Common core covering: glass silk tapes or
extruded filling mixture,
foil wrapping
Concentric conductor: made of bare copper wires with opposing
holding coil made of copper tape,
PETP- Tape
outer sheath: polymer mixture
halogen-free according to VDE 0207 T. 24
Sheath color: orange
Technical data:
Nominal voltage: 06/1 kV
Test voltage: 4000 V
Temperature range: +5°C - +50°C (when laying)
-30°C - +70° C (after laying)
Operating temperature: +90°C (max.)
Bending radius: 10 x cable diameter (fixed)
Tests:
Flammability: according to VDE 0472 T. 804,
test type C (=IEC 332-3)
Insulation maintenance: according to VDE 0472 T. 814 and IEC 331
Functional integrity: according to VDE 0472 T. 804 Sales unit: 1 MTR