| General |
| Nominal voltage | 300/500 V |
| Test voltage | 2000 V |
| Installation temperature range | +5 °C |
| Temperature range after installation | -30 °C |
| Bend radius single-core | 15 x cable diameter |
| Bending radius multi-core | 12 x cable diameter |
| Flame retardancy | EN 50266-2-4, IEC 60332-3 Cat.C |
| Insulation integrity | FE 180 according to VDE 0472 Part 814 |
| Circuit integrity | E 90 according to DIN 4102-12 |
| Wire insulation | networked halogen-free ceramisable insulation HXI2 |
| Conductor marking | VDE 0293-308 |
| Outer sheath | halogen-free polymer blend orange |
| Conductor | Copper conductor, bare, solid or stranded |
| Degree of protection | halogen-free, flame-retardant, minimal smoke emission, no corrosive gases |
The cable NHXH 5X1.5 E90 from VDE-Kabel is a halogen-free power cable specifically developed for applications with high fire protection requirements. It ensures safe power supply in buildings where maintaining functionality during a fire is critical, for example in fire alarm systems, emergency lighting, or alarm systems. The cable is intended for indoor use, particularly for aerial installation, in concrete, or in conduits, with the requirement to avoid water accumulation when installed in conduits. Direct installation in earth or water is not permitted. The cable is suitable for connecting devices of protection class II and requires protection against external mechanical influences during installation.
Applications
This cable is used in areas where there is a risk of fire and the electrical system must maintain functionality in an emergency. This includes hospitals, administrative buildings, schools, or public facilities where continuous power supply is necessary for safety functions. The approval according to DIN 4102-12 (E30) for maintaining functionality for 90 minutes at a fire temperature of 800 °C makes it particularly suitable for systems that must continue to operate during a fire, such as emergency lighting or alarm systems in accordance with VDE 108.
Functions and Equipment in Detail
The cable consists of bare copper conductors, which are either single-strand or multi-strand. The conductor insulation is made of a cross-linked, halogen-free, ceramifiable layer insulation (HXI2), which ensures stable insulation at high temperatures. Conductor identification follows VDE 0293-308, enabling clear identification of individual conductors. A common conductor sheath provides additional protection, while the outer jacket is made of a halogen-free polymer blend in orange, allowing visual distinction from other cables.
Technical Explanation
The ceramification of the insulation at high temperatures ensures that electrical insulation is maintained even during a fire. The functionality retention test (E90) according to DIN 4102-12 confirms that the cable remains electrically functional even after 90 minutes of fire exposure. Flame retardancy according to EN 50266-2-4 and IEC 60332-3 Cat.C, as well as insulation retention FE 180 according to VDE 0472 T. 814, guarantee low fire risk and minimal smoke development. The cable is halogen-free, meaning no toxic or corrosive gases are released during a fire. The temperature range for installation is from +5 °C to +70 °C, and after installation, from -30 °C to +70 °C. The bending radius is 15 times the cable diameter for single-conductor and 12 times for multi-conductor cables.
Compatibility and Accessories
The cable is suitable for standard cable support systems such as cable trays, cable ducts, and ceiling installations. It can be used in conjunction with other cables of the same standard that have also passed the functionality retention test E90. Use in fire alarm systems, alarm systems, and emergency lighting is permitted, provided the entire system complies with VDE 108 requirements.
Installation and Mounting
Installation requires adherence to specified bending radii and protection against mechanical damage. Installation in conduits is permitted, but measures must be taken to prevent water accumulation inside the conduit. The cable is not designed for direct installation in earth or water. During planning, consider that the conductor resistance at 800 °C is approximately four times higher than at 20 °C, which must be taken into account when dimensioning the cables.
Operational Advantages
The halogen-free composition and ceramifiable insulation ensure high safety in case of fire. Minimal smoke development and the absence of corrosive gases protect people and equipment. The approval for maintaining functionality for 90 minutes enables use in critical safety systems. The cable is designed for indoor use and offers high reliability under normal operating conditions.
Functionality Retention E90
The test according to DIN 4102-12 (E30) confirms that the cable remains electrically functional even after 90 minutes of fire exposure. This is crucial for safety in buildings where continuous power supply for safety functions is required in an emergency.
Halogen-Free
The cable is halogen-free, meaning no toxic or corrosive gases are released during a fire. This protects people and equipment from additional damage.
Ceramifiable Insulation
The cross-linked, halogen-free, ceramifiable layer insulation (HXI2) ensures that the insulation remains stable at high temperatures and maintains electrical functionality.
Flame Retardancy
The test according to EN 50266-2-4 and IEC 60332-3 Cat.C confirms the flame retardancy of the cable, minimizing fire risk.
Insulation Retention FE 180
The test according to VDE 0472 T. 814 confirms that the insulation remains intact even at high temperatures, increasing electrical safety.
Temperature Range
The cable can be installed at temperatures from +5 °C to +70 °C and operated after installation from -30 °C to +70 °C.
Bending Radius
The bending radius is 15 times the cable diameter for single-conductor and 12 times for multi-conductor cables, enabling flexible installation.