Installation cable with circuit integrity
Application:
Security installation cable for the transmission of signals and
measurements in control and regulation systems. Where special protection
against fire and fire damage to people and property values ​​and
integrity of the equipment over a period of 30 minutes or
30 - 90 minutes is required. They are not for power-
approved installation purposes and not for direct burial.
Building:
Conductor: solid bare copper wire
0.8 mm in diameter mica tapes
Insulation: cross-linked polymer HI1 according to VDE 0207
23 part
Core identification to VDE 0815
Twisting: 2 cores to the pair and
4 pairs into
bundles in layers common Aderhüllung
Static Screen: plastic laminated
metal foil (metal side inside)
and bare drain wire
Outer sheath: Polyolefin compound HM2
as per VDE 0207 Part 24
halogen-free and flame retardant
sheath color: orange or red than
Fire Alarm Cable
Specifications: 0.8 mm
Rated voltage: 225 V
Test voltage: 300 V
DC loop resistance: 73.2 ohms / km
Current Rating: 5.1A
Operating capacity: 120 nF / km
Insulation resistance: 100 Mohm x km
Capacitive coupling: C1 200 pF
(100 m , 800 Hz):
Attenuation: 1.2 dB / km (800 Hz)
Temperature range: - 5 ° C - + 50 ° C (during installation)
- 30 ° - 70 ° C (after installation)
Operating Temperature: + 70 ° C (max.)
Bending radius: 7,5 x cable diameter
2.5 x cable diameter
for single bending without train
Tests:
Burning characteristics: according to VDE 0472 T. 804
Category C (= IEC 332-1)
Insulation: according to VDE 0472 part 814, IEC 331
integrity: to DIN 4102 Part 12
Corrosivity
Gases: according to VDE 0472 T. 813
Smoke density: according to VDE 0472 T. 816
Category C (= IE
Type: JE-H (ST) H 8x2x0, 8 BMK E30
Quantity: 1 MTR