Further information for VDE-Kabel NHXCH-E30 3 X 70,0/ 35,0 (G024096)
'Halogen-free cable NHXCH FE 180 E 30
with insulation and functional integrity, shielded
Application:
Wherever special protection against fire and fire damage to
people and property is necessary and long emergency times
must be met, such as in airports, hospitals and
schools. Can be used indoors and outdoors, do not
lay directly in soil and water. The development of toxic gases caused by fire
is prevented. Insulation retention of at least
180 minutes and functional retention of at least 30 minutes. Security
for over 30 minutes guarantees, for example, the functionality of
fire detection and alarm systems, security and other
backup lighting.
Construction:
Conductor: Bare copper conductor according to VDE 0295,
round single-wire or multi-wire
50 mm2 are compressed
Mica tape
Core insulation: polymer mixture halogen-free
according to VDE 0207 T. 23
Core identification: according to VDE 0293 (single-wire always in
O version) Filler jacket
Common core covering: Glass silk tape or
extruded Filling mixture
Concentric conductor: made of bare copper wires with opposing
holding coil made of copper tape,
PETP tape
Outer sheath: polymer mixture halogen-free
according to VDE 0207 T. 24
Sheath color: orange
Technical data:
Nominal voltage: 06/1 kV
Test voltage: 4000 V
Temperature range: +5°C - +50°C (when laying)
-30°C - +70°C (after laying)
Operating temperature: +90°C (max.)
Bending radius: 10 x cable diameter
(fixed)
Tests:
Burning behavior: according to VDE 0472 T . 804,
test type C (=IEC 332-3)
Insulation maintenance: according to VDE 0472 T. 814 and IEC 331
Functional maintenance: according to VDE 0472 T. 804 and IEC 332-3
Corrosiveness of the fire gases: according to VDE 0472 T. 813
Smoke gas tight Sales unit: 1 MTR