Heavy rubber cable H07RN-F
to VDE 0282-4
Application: < B>
For connection of equipment under very extreme
loads, both mechanical and thermal point of view.
for example, in agricultural equipment, commercial and fire-hazard
ten operating sites.Next they are for large boilers, heating plates,
hand lamps, electric tools such as circular saws, drills,
home network devices, but also for transportable motors or machines
used on construction sites or farms, etc.,
can also for fixed installation, eg on plaster, in temporary
buildings and barracks, allowed for direct laying aud
components
of lifting equipment, machines, etc.
Structure: < B>
Conductor: Stranded bare copper Class 5
Insulation: rubber mixture according to VDE 0207 T. 20
Core identification to VDE 0293
outer sheath: rubber mixture according to VDE 0207 T. 21
Color: black
Specifications: < B>
Rated voltage: 450/750 V
Test voltage: 2500 V
temperature range: - 25 ° C - + 60 ° C (during installation)
- 40 ° C - +60 ° C (after installation)
Operating temp. +60 ° C (max.)
bending radius: 6 x cable diameter (min.)
Dauerzugbelastung: max.15N/mm 2
taking into account the
total copper cross section
fire: according to VDE 0472 T. 804
type B (= IEC 332-1)
oil resistance of sheath: VDE 0472 T. 803 test A
Ozone resistance: according to VDE 0472 T. 805 Category A or
to VDE 0472 T. 805 A1 Category C
cores x cross-section mm ²: 4 G 4
Cu index (kg / m% ): 15.4
Outer diameter approx: 17.9
weight (kg / m%): 35.7
type: H07RN-F 4G4 50M item: 50 MTR