Further information for VDE-Kabel NA2XS(F)2Y 3 X 1 X 150,0 RM/25 12/20KV (295388)
Application:
For laying in the ground, outdoors (however, the cable must be protected from sunlight), indoors and in cable ducts for power plants, industry and distribution networks. When laying in cable ducts and indoors, it must be taken into account that the PE sheath is not flame-retardant according to VDE 0472 T. 804, test type B.
The cable is suitable for unfavorable operating conditions, especially if the penetration of water in the longitudinal direction must be avoided after mechanical damage.
Structure:
Conductor: bare aluminum conductor in accordance with
VDE 0295, (RM) round,
multi-wire, extruded
inner conductive layer
Core insulation: VPE (cross-linked polyethylene)
extruded outer conductive layer gap sealing
(conductive tape and swelling tape)
Shield: copper wires and cross-conductive spiral
made of copper
foil banding
Outer jacket: black PE
Technical data:
Nominal voltage: 6/10 kV, 12/20 kV and 18/30 kV
Test voltage: 21 kV AC/5 min. at Uo/U=6/10 kV
30 kV AC/5 min. at Uo/U=12/20 kV
45 kV AC/5 min. at Uo/U=18/30 kV
Temperature range: -20 °C - +70 °C (during installation)
-30 °C - +70 °C (after installation)
Operating temperature: +90 °C (max.)
Bending radius: 15 x cable diameter min.