Further information for Waskönig+Walter NYM-J 5X16 TR - NYM 5x16 sqmm RM PVC insulated sheathed cable
Sheathed cables NYM-J
according to VDE 0250 part 204
Application:
For installations in the home, in industry, in the open, in dry and wet areas, on, in and under plaster, in masonry and in concrete (except vibrated or compressed concrete). For outdoor use, the cable must be protected from direct sunlight.
Building:
Conductor: bare copper wire
- 10 mm ² solid
> 10 mm ² stranded
Insulation: PVC according to VDE 0207 part 4
Marking: according to VDE 0293
Filling compound
Sheath: Grey PVC
Specifications:
Rated voltage: 300/500 V
Test voltage: 2000 V
Temperature
range: +5 ° C +70 ° C (during installation)
-40 ° C +70 ° C (after installation)
Operating temp. +70 ° C (max.)
Bending radius: 4 x cable diameter
(Fixed installation)
* Ajar VDE
Cable NYM-J
according to VDE 0250 part 204
Application:
For installations in the home, in industry, in the open, in dry
and wet locations, on, in and under plaster, in masonry and concrete
(Except vibrated or compressed concrete). For outdoor applications
tion must protect the line from direct sunlight are
the.
Building:
Conductor: bare copper wire
- 10 mm ² solid
> 10 mm ² stranded
Insulation: PVC according to VDE 0207 part 4
Marking: according to VDE 0293 core covering
Sheath: Grey PVC
Specifications:
Rated voltage: 300/500 V
Test voltage: 2000 V
Temperature range: +5 ° C +70 ° C (during installation)
-40 ° C +70 ° C (after installation)
Operating temp. +70 ° C (max.)
Bending radius: 4 x cable diameter
(Fixed installation)
* VDE - based
Number of cores x cross-section mm ²: 5 x 16.0 TR
Weight (kg / m%): 124.9
Outer diameter approx: 24.4
Copper content (kg / m%): 76.8
Type: NYM-J 5X16 TR
Quantity: 1 MTR