Further information for Diverse Y(ST)H 2X2X0,8 HALOF - EIB BUS cable 2x2x0 8 green halogen free 500m drum
Preferably in the construction of intercoms and extensions inside buildings, but also outdoors for permanent installation on buildings. These cables are specially designed for fire alarm systems.
Structure:
Conductor: single-wire bare copper conductor,
0.8 mm diameter
Core insulation: PVC
Marking: in accordance with VDE 0815
Stranding: cores in pairs Pairs in layers
Static shield: plastic-coated metal foil
with drain
wire Foil
outer sheath: green PVC with
'fire alarm cable' imprint
Technical data:
Nominal voltage: 300 V
Test voltage: 800 V
Loop resistance: 73.2 Ohm/km
Current carrying capacity: 5.1 A
Operating capacity: 100 nF/km
Insulation resistance: 100 MOhm x km
Capacitive
coupling: K1 (800 Hz, 100 m) 300 pF
Line attenuation: approx. 1.1 dB/km (800 Hz)
Temperature range: -5 °C - +50 °C (when laying)
-30 °C - +70 °C (after laying)
Operating temperature: +70 °C (max.)
Bending radius: 7.5 x Cable diameter
2.5 x cable diameter
for one-time bending without tension
Flame retardancy: according to VDE 0472 T. 804
test type B (=IEC 332-1).