| Complementary |
| Reset time | 1750 ms |
| Maximum switching voltage | 250 V AC/DC |
| [Un] rated nominal voltage | 24...240 V AC/DC 50/60 Hz, non self-powered |
| Supply voltage limits | 20.4…264 V AC/DC |
| operating voltage tolerance | - 15 % + 10 % Un |
| Output contacts | 2 C/O |
| nominal output current | 5 A |
| delay at power up | 0.6 s |
| Measurement accuracy | +/- 10 % of the full scale value; +/- 20 % for the HS range |
| Repeat accuracy | +/- 2 % for time delay |
| Measurement error | 0.5 %/°C with temperature variation |
| Maximum cable distance between devices | 100 m |
| Sensitivity scale | 0.25...5 kOhm LS (Low Sensitivity); 5...100 kOhm St (Standard Sensitivity); 50...1000 kOhm HS (High Sensitivity) |
| Sensitivity adjustment | 5…100 % |
| Maximum supply current for sensors | 1 mA |
| Cable capacitance | 1 nF at HS (High Sensitivity) for probe cable; 2.2 nF at St (Standard Sensitivity) for probe cable; 4.7 nF at LS (Low Sensitivity) |
| Marking | CE : 73/23/EEC; CE : EMC 89/336/EEC |
| Overvoltage category | III conforming to IEC 60664-1 |
| Insulation resistance | > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5; > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1; > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5; > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1; > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5; > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1 |
| [Ui] rated insulation voltage | 250 V conforming to IEC 60664-1 |
| Operating position | Any position without derating |
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (20 AWG...11 AWG) solid without cable end; Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...12 AWG) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Polycarbonate |
| Local signalling | LED (yellow) for relay ON; LED (green) for power ON; LED (yellow) for timer ON |
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| Electrical durability | 100000 cycles |
| Mechanical durability | 30000000 cycles |
| Safety reliability data | B10d = 170000; MTTFd = 182.6 years |
| Width | 35 mm |
| Control type | Without test button |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Immunity to microbreaks | 100 ms DC; 90 ms AC |
| Electromagnetic compatibility | Emission standard for industrial environments conforming to IEC 61000-6-4; Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3; Immunity for industrial environments conforming to NF EN/IEC 61000-6-2 |
| Standards | IEC 60255-6 |
| Product certifications | CSA; GL; UL; C-Tick; GOST |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air temperature for operation | -20…50 °C |
| Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Dielectric test voltage | 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5; 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1 |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Control Relays |
| Relay type | Level control relay |
| Product or component type | Level control relay |
| Relay name | RM35L |
| Relay monitored parameters | Detection by resistive probes |
| time delay | Adjustable 0.1...5 s, +/- 10 % Tt- time delay upon fault |
| Switching capacity in VA | 1250 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum switching current | 5 A AC/DC |
| power consumption | 5 VA AC |
| Measurement range | 250 Ohm...1 MOhm |
| Utilisation category | AC-12 conforming to IEC 60947-5-1; AC-13 conforming to IEC 60947-5-1; AC-14 conforming to IEC 60947-5-1; AC-15 conforming to IEC 60947-5-1; DC-12 conforming to IEC 60947-5-1; DC-13 conforming to IEC 60947-5-1 |
| Contacts type and composition | 2 C/O |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.400 cm |
| Package 1 Width | 7.800 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 134.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 48 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.155 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 384 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 65.660 kg |
Harmony Control. This level relay monitors the level of conductive, non-flammable liquids (conductive measuring principle) as a limit switch. It can also be used to control liquid levels in a 2-point control during filling and emptying. For this purpose, additional conductive level electrodes are hung in the tank. The measuring principle enables the distinction between liquid and foam. Two relay changeover switches are available for reporting, which can be loaded up to 5 A. The limit value can be set for the resistance value (250 Ohm-1 MOhm) and a time delay for the relays. The settings are made using controls on the front, which can be protected against changes under a transparent cover. 3 LEDs show the device status. The wide-voltage power supply (24-240 VAC/DC) enables universal use. The cable connection is made using screw terminals.