| Complementary |
| [Us] rated supply voltage | 24...240 V AC/DC 50/60 Hz, non self-powered |
| Supply voltage limits | 20.4…264 V AC/DC |
| Maximum power consumption in VA | 3 VA |
| Maximum power consumption in W | 1 W |
| Measurement range | 2...20 A AC |
| Maximum measuring cycle | 30 ms measurement cycle as true rms value |
| Hysteresis | 15 % fixed of threshold setting |
| Repeat accuracy | +/- 0.5 % for input and measurement circuit |
| Measurement error | +/- 0.05 %/°C with temperature variation; < 1 % over the whole range with voltage variation |
| Time delay type | Without |
| Response time | < 200 ms (in the event of a fault) |
| Power on Delay | 600 ms |
| Output contacts | 1 C/O |
| nominal output current | 5 A |
| Maximum switching voltage | 250 V AC/DC |
| Switching capacity in VA | 1250 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Electrical durability | 100000 cycles |
| Mechanical durability | 30000000 cycles |
| operating voltage tolerance | - 15 % + 10 % Un |
| Control circuit frequency | 40...70 Hz sinusoidal |
| Measurement accuracy | +/- 10 % of the full scale value |
| Polarity | Yes DC |
| Threshold setting | 10...100 % |
| Input current | 100000 mA permanent at 25 °C; 300000 mA non repetitive < 3 s at 25 °C |
| Insulation | Between supply and measurement |
| Contacts material | Cadmium free |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Electromagnetic compatibility | Emission standard for industrial environments conforming to IEC 61000-6-4; Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3; Immunity for industrial environments conforming to NF EN/IEC 61000-6-2 |
| Standards | IEC 60255-6 |
| Product certifications | GL; C-Tick; GOST; UL; CSA |
| Marking | CE : 73/23/EEC; CE : EMC 89/336/EEC |
| Ambient air temperature for storage | -40…70 °C; -40…70 °C |
| Ambient air temperature for operation | -20…50 °C |
| Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Overvoltage category | III conforming to IEC 60664-1 |
| Dielectric test voltage | 2 kV AC 50 Hz |
| Insulation resistance | > 500 MOhm at 500 V DC conforming to IEC 60255-5 |
| [Ui] rated insulation voltage | 400 V conforming to IEC 60664-1 |
| Operating position | Any position without derating |
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (20 AWG...11 AWG) solid without cable end; Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...12 AWG) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Polycarbonate |
| Local signalling | LED (green) for power ON; LED (yellow) for relay ON |
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| Height | 90 mm; 88.9 mm |
| Width | 17.5 mm; 17.8 mm |
| Depth | 72 mm; 71.1 mm |
| Net weight | 0.11 kg; 0.11 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Control Relays |
| Relay type | Current control relay |
| Product or component type | Current control relay |
| Relay name | RM17JC |
| Relay monitored parameters | Overcurrent detection |
| Control type | Without test button |
| Contacts type and composition | 1 C/O |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.800 cm |
| Package 1 Width | 9.700 cm |
| Package 1 Length | 10.400 cm |
| Package 1 Weight | 117.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 32 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.200 kg |
Harmony Control. This current monitoring relay has an integrated current transformer so that the line to be monitored is detected without contact. To do this, the line must be fed through the hole in the transformer. The adjustable current limit value of 2-20 A is also monitored for exceedance. A relay changer is available for reporting, which can be loaded up to 5 A. The function of the output relay can be inverted using a wire bridge. Two LEDs show the status. The width is 17.5 mm and it is mounted on the top hat rail. Supply voltage 24-240 VAC/DC (50-60 Hz).