| Complementary |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| [Ith] conventional free air thermal current | 20 A (at 55 °C) for power circuit |
| Irms rated making capacity | 50 A AC conforming to NF C 63-110; 50 A AC conforming to IEC 60947 |
| Rated breaking capacity | 40 A at |
| [Icw] rated short-time withstand current | 40 A 55 °C for power circuit |
| Associated fuse rating | 20 A gI at |
| Average impedance | 4 mOhm - Ith 20 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to BS 5424; Power circuit: 690 V conforming to IEC 60947; Power circuit: 690 V conforming to UL 508; Power circuit: 690 V conforming to VDE 0110 group C; Power circuit: 690 V conforming to CSA C22.2 No 14 |
| Mounting support | Rail |
| Standards | EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1 |
| Product certifications | CB Scheme; CE; UKCA; EAC; cULus |
| Connections - terminals | Connector 1 cable(s) 1.5…6 mm²solid; Connector 2 cable(s) 1.5…4 mm²solid; Connector 1 cable(s) 0.5…6 mm²flexible without cable end; Connector 2 cable(s) 0.35…2.5 mm²flexible without cable end; Connector 1 cable(s) 0.35…6 mm²flexible with cable end; Connector 2 cable(s) 0.35…1.5 mm²flexible with cable end |
| Tightening torque | Power circuit: 0.8 N.m - on connector - with screwdriver pozidriv No 1 |
| Operating time | 6...8 ms coil de-energisation and NO opening; 7...14 ms coil energisation and NO closing |
| Mechanical durability | 10 Mcycles |
| Maximum operating rate | 1200 cyc/h |
| Control circuit voltage limits | Operational: 0.85...1.1 Uc at 50/60 Hz (at |
| Inrush power in VA | 16 VA 50/60 Hz (at 20 °C) |
| Hold-in power consumption in VA | 4.2 VA 50/60 Hz (at 20 °C) |
| Heat dissipation | 1.4 W at 50/60 Hz |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP2X conforming to VDE 0106 |
| Protective treatment | TC conforming to IEC 60068; TC conforming to DIN 50015 |
| Ambient air temperature for operation | -20…50 °C |
| Ambient air temperature for storage | -50…70 °C |
| Operating altitude | 2000 m without derating |
| Height | 56 mm |
| Width | 27 mm |
| Depth | 55.5 mm |
| Net weight | 0.132 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Product name | TeSys SK |
| Product or component type | Mini contactor |
| Device short name | LC1SKGC |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-1; AC-3 |
| power pole contact composition | 2P |
| Pole contact composition | 2 NO |
| [Ie] rated operational current | 5 A at |
| [Ue] rated operational voltage | Power circuit: 690 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.400 cm |
| Package 1 Width | 6.000 cm |
| Package 1 Length | 7.000 cm |
| Package 1 Weight | 127.000 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 40 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 15.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.257 kg |
The mini contactor LC1SKGC200P7 from the TeSys series by Schneider Electric is a compact switching device for controlling electrical loads in industrial, infrastructure, and building technology applications. It is used for motor control as well as switching resistive loads and is designed for use in simple machine control systems. The device features a control coil rated for 230 V AC and is designed for operation in networks with 50/60 Hz. The rated operational current is 5 A for usage category AC-3 and an operating voltage of 400 V AC, with the rated operational voltage of the circuit reaching up to 690 V AC. Control is achieved via an electronic interface that can be easily connected to PLC systems.
Applications
This contactor is suitable for applications in industry, infrastructure projects, and building installations where reliable and compact load control is required. It is particularly suited for small to medium-sized motors and resistive loads operated in continuous or intermittent operating cycles. Mounting is done on a rail, enabling flexible integration into existing control panels. The operating temperature range is between -20 °C and 50 °C, and the device can be used up to an operating altitude of 2,000 m without performance reduction.
Functions and Equipment in Detail
The device features a contact configuration of 2P with 2 normally open contacts (2 S). The mechanical life expectancy is 10 million switching cycles, with a maximum operating rate of 1,200 switching operations per hour. The operating time is 6–8 ms for coil de-energization and NO opening, and 7–14 ms for coil energization and NO closing. The pickup power is 16 VA, and the holding power consumption is 4.2 VA at 50/60 Hz and 20 °C. The heat dissipation of the device is 1.4 W.
Technology Explained Simply
The control circuit voltage of 230 V AC allows for easy integration into existing control systems. The rated insulation voltage is 690 V and complies with international standards such as IEC 60947, VDE 0110, UL 508, and CSA C22.2 No. 14. The conventional thermal current (Ith) is 20 A at 55 °C in free air, describing the thermal load capacity of the device under realistic operating conditions. The rated make capacity and nominal breaking capacity are 50 A and 40 A, respectively, defining the electrical strength during switching operations. The associated fuse is specified as 20 A gI.
Compatibility and Accessories
Overvoltage limiters are available for this contactor, enhancing the reliability of the control circuit. These include the LA4SKC1U (24–250 V DC, diode), LA4SKE1U (110–250 V AC/DC), and LA4SKE1E (varistor). These components can be used for protection against transient voltage spikes, extending the lifespan of the contactor and connected devices.
Mounting and Installation
Mounting is done on a rail, with device dimensions of 27 mm (width) × 56 mm (height) × 55.5 mm (depth). Connections are made via plugs, supporting rigid cables with cross-sections of 1.5 to 6 mm² (plug 1) and 1.5 to 4 mm² (plug 2), and flexible cables with cross-sections of 0.5 to 6 mm² (without cable end) and 0.35 to 2.5 mm² (without cable end), as well as 0.35 to 6 mm² (with cable end) and 0.35 to 1.5 mm² (with cable end). The tightening torque is 0.8 Nm, with mounting using a screwdriver in position No. 1.
Advantages in Operation
The contactor is characterized by a high mechanical life expectancy and robust construction. Its compact design enables efficient space utilization in control enclosures. Certifications according to CB regulation, CE, UKCA, EAC, and cULus, along with compliance with standards EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No. 60947-4-1, ensure safety and reliability in use. The TC coating complies with IEC 60068 and DIN 50015, ensuring resistance to environmental influences. The protection rating IP2x complies with VDE 0106, providing protection against finger contact and against solid objects larger than 12.5 mm.