| Complementary |
| Assembly style | With heat sink |
| Function available | Integrated bypass |
| Supply voltage limits | 342…456 V |
| Supply frequency | 50...60 Hz - 5...5 % |
| Network frequency | 47.5...63 Hz |
| [Uc] Control circuit voltage | Built into the starter |
| Starting time | Adjustable from 1 to 10 s |
| Deceleration time symb | Adjustable from 1 to 10 s |
| Starting torque | 30...80 % of starting torque of motor connected directly on the line supply |
| Discrete input type | Logic (LI1, LI2, BOOST) stop, run and boost on start-up functions |
| Discrete input voltage | 24...40 V |
| Discrete input logic | Positive LI1, LI2, BOOST at State 0: < 5 V and 13 V, >= 0.5 mA |
| Discrete output current | 2 A DC-13; 3 A AC-15 |
| Discrete output type | Open collector logic LO1 end of starting signal; Relay outputs R1A, R1C NO |
| Discrete output voltage | 24 V (voltage limits: 6...30 V) open collector logic |
| Minimum switching current | 10 mA at 6 V DC for relay outputs |
| Maximum switching current | Relay outputs: 2 A at 250 V AC cos phi = 0.5 and L/R = 20 ms inductive load; Relay outputs: 2 A at 30 V DC cos phi = 0.5 and L/R = 20 ms inductive load |
| Display type | 1 LED (green) for starter powered up; 1 LED (yellow) for nominal voltage reached |
| Tightening torque | 1.9…2.5 N.m; 0.5 N.m |
| Marking | CE |
| Operating position | Vertical +/- 10 degree |
| Height | 124 mm |
| Width | 45 mm |
| Depth | 131 mm |
| Net weight | 0.42 kg |
| Compatibility code | ATS01N2 |
| Power range | 4…6 kW at 380…440 V 3 phases |
| Motor starter type | Soft starter |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-4-2 |
| Product certifications | CCC; UL; GOST; CSA; C-Tick |
| IP degree of protection | IP20 |
| Pollution degree | 2 conforming to EN/IEC 60947-4-2 |
| Vibration resistance | 1 gn (f= 13…150 Hz) conforming to EN/IEC 60068-2-6; 1.5 mm peak to peak (f= 3…13 Hz) conforming to EN/IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms conforming to EN/IEC 60068-2-27 |
| Relative humidity | 5…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3 |
| Ambient air temperature for operation | -10…40 °C (without derating); 40…50 °C (with current derating of 2 % per °C) |
| Ambient air temperature for storage | -25…70 °C conforming to EN/IEC 60947-4-2 |
| Operating altitude | 1000 m with current derating of 2.2 % per additional 100 m |
| Logistical informations |
| Country of origin | DE |
| Main |
| Range of product | Altistart 01 |
| Product destination | Asynchronous motors |
| Product or component type | Soft starter |
| Product specific application | Simple machine |
| Device short name | ATS01 |
| Network number of phases | 3 phases |
| [Us] rated supply voltage | 380...415 V - 10...10 % |
| Motor power kW | 5.5 kW, 3 phases at 380...415 V |
| IcL starter rating | 12 A |
| Utilisation category | AC-53B conforming to EN/IEC 60947-4-2 |
| Current consumption | 60 A at nominal load |
| Type of start | Start with voltage ramp |
| Power dissipation in W | 4 W at full load and at end of starting; 124 W in transient state |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.500 cm |
| Package 1 Width | 15.200 cm |
| Package 1 Length | 17.500 cm |
| Package 1 Weight | 525.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 14 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.842 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 112 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 74.012 kg |
Altistart 01 for gentle starting and stopping. Soft starter for asynchronous motors. Rated current 12 A, power 230V 2.2 kW, power 400V 5.5 kW. 400 V, 3-phase network, 50/60 Hz, internal control voltage. The soft starter enables gentle starting of three-phase asynchronous motors and prevents current peaks in the start-up phase as well as mechanical load surges. Typical applications: conveyor belts, conveyors, pumps, fans, compressors, etc. Extremely simple commissioning, integrated bypass, optional signal outputs or internal or external control voltage, boost function for high breakaway torque.