| Complementary |
| Input voltage limits | 22...30 V |
| Maximum power dissipation in W | 15 W |
| Activation threshold | (Uin-1) V and 22 V min |
| Charging time | 25 s |
| Number of output channels | 1 |
| Current consumption | 0.6 A on load; 0.1 mA no load; |
| Output protection type | Against overload, protection technology: > 45 A; Against short-circuits, protection technology: power-supplied mode, automatic reset; Against undervoltage, protection technology: tripping if U < 19 V |
| Connections - terminals | For input connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² 20 AWG...8 AWG; For output connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² 20 AWG...8 AWG; For diagnostic relay: removable screw terminal block, connection capacity: 1 x 2.5 mm² 14 AWG |
| Fixing mode | By clips on 35 mm symmetrical DIN rail, operating position: horizontal; By clips on 35 mm symmetrical DIN rail, operating position: vertical |
| Output coupling | Parallel |
| Operating altitude | 2000 m |
| Marking | CE |
| Name of test | Electrostatic discharges conforming to IEC 61000-4-2; Emission conforming to IEC 61000-6-3; Induced electromagnetic field conforming to IEC 61000-4-6 level 3; Radiated electromagnetic field conforming to IEC 61000-4-3 level 3; Rapid transient conforming to IEC 61000-4-4 level 3; Surge conforming to IEC 61000-4-5 level 2; Conducted/radiated emissions conforming to EN 55022 class B, 20 % |
| Local signalling | 1 LED (green) for buffer ready; 1 relay for buffer ready |
| Net weight | 1.2 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Product certifications | RCM; EAC |
| Standards | UL 508; CSA C22.2 No 60950-1 |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Environmental characteristic | EMC conforming to IEC 61000-6-3; EMC conforming to IEC 61000-6-2; Safety conforming to IEC 60950-1; Safety conforming to EN/IEC 61204-3 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Dielectric strength | 500 V between input and ground; 500 V between output and ground |
| Overvoltage category | Class II conforming to VDE 0106-1 |
| Relative humidity | 0…90 % during operation; 0…95 % during storage |
| MTBF reliability | 1119603 H at 24 V DC with UTE C80-810 calculation method |
| Vibration resistance | 2 gn (f= 11.9…150 Hz) conforming to IEC 61131-2; 3.5 mm (f= 3…11.9 Hz) conforming to IEC 61131-2 |
| Logistical informations |
| Country of origin | PH |
| Main |
| Range of product | Phaseo |
| Product or component type | Buffer module |
| Input voltage | 24...28.8 V DC |
| Output voltage | (Uin-0.25) V in nominal mode DC; (Uin-1) V in buffer mode DC |
| Maximum output current | 40 A |
| Holding time | 0.1 s at 40 A; 6 s at 0.5 A |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 11.500 cm |
| Package 1 Width | 17.000 cm |
| Package 1 Length | 18.200 cm |
| Package 1 Weight | 1.401 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 60 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 97.060 kg |
The Modicon ABL8 Universal series of switched-mode power supplies are ideal for most industrial applications and are designed in particular for direct current supply in automation applications. The ABL8 product family impresses with its compact and robust design and includes power supplies with an output voltage of 24V DC. This functional module for the Modicon ABL8 power supplies is used for short-term buffering of a 24V DC supply. This means that micro-interruptions in the supply networks can be compensated and do not lead to faults in automation applications. Depending on the power requirement, a buffer time of up to 2 seconds at 2 A or 0.2 seconds at 20 A can be achieved. The maximum current is 40A. An LED display provides information on the status of the buffer module and a diagnostic relay indicates the status. Suitable for international use due to the large number of existing product standards and certifications. Thanks to the Green Premium ecolabel, you can obtain detailed information on material content, environmental impact and circular economy that supports your sustainability goals.