| Additional features |
| Form factor | Flex |
| Mounting mode | By screws (clamps) |
| Electrical connection (voltage sensing & power supply) | Wires with cable ends |
| Cable cross-section | 1 fixed cable 1.5…16 mm²; 2 stranded cable 1.5…2.5 mm²; 2 fixed cable 1.5…2.5 mm²; 1 stranded cable 1.5…16 mm² |
| Cable length | 0,25 m |
| Supply voltage | 220 - 240 V AC, ± 20 %, between phase and neutral; 380 - 415 V AC, ± 20 %, between phases |
| Network frequency | 50 Hz; 60 Hz |
| Maximum power consumption | 2 VA |
| Standards | IEC 61557-12; IEC 61010-1; IEC 61010-2-030; IEC 61326-1; ETSI EN 300 328; ETSI EN 301 489-1 |
| Product certifications | IEC; DNV Marine |
| Height | Sensor element: 20 mm |
| Width | Sensor element: 54 mm |
| Depth | Sensor element: 46.6 mm |
| Product weight | 40 g |
| Colour | White (RAL 9003) |
| Compatibility code | PowerTag A9 P63 |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | PowerLogic |
| Product name | PowerTag A9 F63 |
| Product or component type | Energy sensor |
| Poles | 3P + N |
| [Imax] max. current | 63 A |
| [Ib] base current | 10 A |
| Input current | 40 mA |
| Saturation current | 130 A |
| Product-specific application | cost allocation; load monitoring; overload alarm; circuit monitoring; energy management |
| Concentrator compatibility | Panel Server Entry; Panel Server Universal; Panel Server Advanced; Harmony Hub; Wiser hub Generation 2; Acti 9 Smartlink SI B; Acti 9 Smartlink SI D; Acti 9 PowerTag Link; Acti 9 PowerTag Link HD |
| Application | Building: power circuit breaker voltage monitoring; Building: cost allocation; Building: overload alarm |
| Compatible product family | Acti9 Vigi DT40; Acti9 Vigi iC40; Acti9 Vigi iDT40; Acti9 Vigi N40; Acti9 Vigi C40; Acti9 Vigi iC60; Acti9 Acti9 iDD40; Acti9 Acti9 iDD40 XA; Acti9 Acti9 iCV40 XA; Acti9 Vigi iDPN; Acti9 Acti9 iCV40; Acti9 Vigi iTG40; Acti9 Vigi iCG40 |
| Measured value type | Voltage; Active energy; Active power; Current; Power factor |
| Accuracy class | Class 1 current corresponds to IEC 61557-12; Class 0.5 voltage corresponds to IEC 61557-12; Class 1 active power corresponds to IEC 61557-12; Class 1 active energy corresponds to IEC 61557-12; Class 1 power factor corresponds to IEC 61557-12 |
| Mounting location | Top or bottom |
| Mounting bracket | for circuit breaker |
| Product application | Switchgear |
| Event management | Voltage drop with measured current during voltage drop |
| Transmission medium | Radio frequency 2.4…2.4835 GHz corresponds to IEEE 802.15.4 |
| Transmit power | 10 mW |
| Mounting |
| Conformity marking | CE |
| Policies | 2014/53/EU - Radio Equipment Directive |
| Operating altitude | 0 - 2.000 m |
| Operating ambient temperature | -25…60 °C |
| Ambient temperature during storage | -40…85 °C |
| Over voltage category | III corresponds to IEC 61010-1 |
| Measurement category | Category III corresponds to IEC 61010-2-030 |
| Degree of protection (IP) | IP20 complies with IEC 60529 |
| Degree of protection (IK) | IK05 |
| Pollution degree | 3 |
| Relative humidity | 0…95 % at 45 °C corresponds to IEC 60721-3-3 |
| Vibration resistance | 3M4 corresponds to IEC 60721-3-3 |
| Electromagnetic compatibility | Industrial electromagnetic environment complies with IEC 61326-1; Radiated disturbances comply with ETSI EN 301 489-17; Electromagnetic emission complies with IEC 62311 |
| Environmental properties | dust resistant Class 3S3 corresponds to IEC 60721-3-3; salt fog Class 3C2 corresponds to IEC 60721-3-3; for indoor use |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 5,000 cm |
| VPE 1 width | 6,000 cm |
| VPE 1 length | 8,500 cm |
| Packaging weight (Lbs) | 68,000 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 48 |
| VPE 2 height | 15,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 3,625 kg |
The PowerTag Energy F63 3P+N is a wirelessly communicating energy meter. With its flexible design, it is suitable for 3P+N measuring points with a nominal power of 63A or less. The energy meter must be connected to a concentrator or a gateway. It is specially designed for energy management, load monitoring and availability applications. It includes accurate real-time measurements of active energy, active power, current, voltage and power factor. With 2 quadrant energy measurement. In case of a power failure, it sends a voltage loss alarm and the value of the current per phase before being switched off. PowerTag Energy 63A complies with the IEC 61557-12 standard. It is a PMD-I/DD/K55/1. The accuracy class is Class 1. The Imax maximum current is 63A. The Ib base current is 10A. The saturation current is 130A and the actual inrush current is 40mA. The Un rated voltage is phase-neutral 220VAC to 240VAC +/- 20% and phase-phase 380VAC to 415VAC +/- 20%. The maximum consumption is less than or equal to 2VA. It can be mounted either on the top or bottom of the protective device. The product color is white (RAL9003). The weight is 40 g. The protection class is IP20 and IK05. The operating temperature is between -25°C and +60°C. The storage temperature is between -40°C and +85°C.