| Complementary |
| Test function | Local; Remote test |
| Monitoring | Electronics (continuous) ; Power supply (continuous) ; Relay/sensor link (continuous) |
| Type of measurement | Earth fault current internal measurement, range: 80...100 % |
| Tamperproof of settings | Protected by sealable cover |
| Wire stripping length | Auxiliary power supply: 7 mm for top connection; Fault: 8 mm for bottom connection; Relay test and fault reset: 5 mm for bottom connection; Sensor: 5 mm for top connection; Voltage presence: 8 mm for bottom connection |
| Tightening torque | Auxiliary power supply: 0.6 N.m top; Fault: 0.6 N.m bottom; Relay test and fault reset: 0.25 N.m bottom; Sensor: 0.25 N.m top; Voltage presence: 0.6 N.m bottom |
| 9 mm pitches | 6 |
| Standards | EN/IEC 60947-2 Annex M; EN/IEC 60755; UL 1053; CAN/CSA C22.2 No. 144 |
| Width | 54 mm |
| Height | 81 mm |
| Depth | 74 mm |
| Net weight | 0.3 kg |
| IP degree of protection | IP40 on front face: conforming to EN/IEC 60529; IP30 on side parts: conforming to EN/IEC 60529; IP20 on connection terminals: conforming to EN/IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Mechanical robustness | Fire resistance conforming to IEC 60695-2-1; IK protection 2 joules: IK07 conforming to EN 50102; Vibrations 13.2...100 Hz: 0.7 g; Vibrations 2...13.2 Hz: +/- 1 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Overvoltage category | IV |
| Electrical shock protection class | Class II |
| Electromagnetic compatibility | Conducted and radiated emissions: , B, conforming to CISPR 11; Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6; Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2; High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5; Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4; Radiated susceptibility: , 3, conforming to IEC 61000-4-3 |
| Relative humidity | 95 % at 55 °C |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Ambient air temperature for operation | -35…70 °C |
| Ambient air temperature for storage | -55…85 °C |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | VigiPacT |
| Device short name | RH99M |
| Product or component type | Monitoring relay |
| Relay application | Monitoring relay |
| Mounting support | DIN rail |
| Type of setting | Selector |
| Residual earth-leakage sensitity adjustment type | Adjustable 9 settings |
| Earth-leakage sensitivity | 0.03…30 A |
| Earth-leakage time delay | Instantaneous for 0.03 A; Adjustable 9 settings 0…4.5 s for 0.03…30 A |
| Threshold setting | 0.03...30 A alarm |
| Current sensors compatibility | VigiPacT TOA earth leakage current sensor; VigiPacT A earth leakage current sensor; VigiPacT L earth leakage current sensor |
| [Ithe] conventional enclosed thermal current | 8 A |
| Minimum load | 10 mA at 12 V |
| [Us] rated supply voltage | 220...240 V AC 50/60 Hz 55...110 % |
| Power consumption in VA | 4 VA |
| Monitored distribution system | 1000 V - AC at 50/60 Hz (maximum) ; 1000 V - AC at 400 Hz (maximum) |
| Earthing system | TT; TN-S |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.800 cm |
| Package 1 Width | 8.600 cm |
| Package 1 Length | 9.200 cm |
| Package 1 Weight | 263.400 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 36 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.882 kg |
VigiPacT RH99M is a residual current monitoring relay for DIN rail mounting. It monitors the drop in electrical insulation due to aging of cables or extensions in the installation. It measures the leakage current in an electrical installation through its associated toroidal transformer. When the residual current operating threshold is exceeded, a control signal is issued by the relay. The operating supply voltage is 220/240VAC 50/60Hz. The current sensitivity is selectable with 9 thresholds from 30 mA to 30 A. The time delay is selectable with 9 settings from instantaneous to 4.5s. There is an automatic reset after a fault has been cleared. The monitored voltage of the distribution network is up to 1000 VAC 50/60/400 Hz. It is installed on a DIN rail in a control cabinet and has an IP40 protection rating. It must be connected to a compatible Schneider Electric Type A toroidal or rectangular sensor.