Connection of round conductors, fine-stranded without ferrule
1,5 ‐ 16 mm²
Connection of stranded wires, fine-stranded with ferrule
1,5 ‐ 50 mm²
Cross-section round conductor
1,5 ‐ 16 mm²
Maximum power dissipation
26 W
Power loss per fuse element (max.)
9 W
Copper content (kg/piece)
0,26
PCF/VE (Cradle-to-Gate)
5,49
For panel mounting
With electronic fuse monitoring (ESÜ)
The Rittal RX 9363425 is an NH fuse switch disconnector in size 000, specifically designed for mounting plate installation. It serves as a power disconnector in industrial electrical installations and enables the safe disconnection of circuits using NH fuse inserts. The version with electronic fuse monitoring (ESÜ) allows continuous monitoring of the fuse status, thus enhancing operational safety and maintenance efficiency. The disconnector is designed for a rated operational voltage of 690 V AC and complies with standards IEC/DIN EN 60 947-3 as well as DIN EN 60 269-2 for fuse inserts.
Applications
This disconnector is intended for use in industrial plants where safe and monitorable power disconnection is required. It is particularly suitable for applications with high safety requirements, such as in manufacturing, energy supply, or process automation. The 3-pole configuration enables disconnection of three-phase AC circuits. The usage categories include AC-23B (400 V/100 A), AC-21B (500 V/100 A), AC-21B (690 V/100 A), and DC-22B (250 V/100 A), covering a wide range of application scenarios.
Functions and Equipment in Detail
The disconnector's cover is lockable and sealable, preventing unauthorized manipulation and increasing operational safety. Visual fuse monitoring allows direct status checking of the fuse. Secure voltage testing is performed via integrated test points on the cover, accessible through a separate opening. This ensures risk-free testing without fully opening the cover. A parking position for the cover facilitates maintenance work, as the cover can be held in a stable, half-open position.
Technology Explained Simply
The disconnector features a frame terminal as the connection type, designed for connecting round conductors. The permissible cross-sections range from 1.5 to 16 mm² for round conductors without wire end ferrules, and up to 50 mm² when using wire end ferrules. The rated insulation voltage Ui is 1,000 kV, ensuring high insulation strength. The protection rating IP 2XB according to IEC 60 529 protects against finger contact and vertical dripping water, making the disconnector suitable for use in slightly damp environments. The material consists of polyamide (PA 6) with flammability rating according to UL 94; the contact strips are made of electrolytic copper, silver-plated, ensuring high conductivity and corrosion resistance.
Compatibility and Accessories
The disconnector is designed for NH size 000 and requires corresponding fuse inserts. As suitable accessories, the microswitch RX 9365500 is offered, which is suitable for NH disconnectors of size 000. The connection plugs for electronic fuse monitoring are included in the delivery scope.
Mounting and Installation
The disconnector is intended for mounting plate installation and can be secured to mounting plates without tools. The cable exit is at the top and bottom, enabling flexible installation in enclosures. The operating temperature range is between -5 °C and 35 °C, while the storage temperature range extends from -25 °C to 70 °C. Dimensions are 53 mm (width) × 307.3 mm (height) × 80.1 mm (depth).
Advantages in Operation
The integrated electronic fuse monitoring (ESÜ) enables continuous monitoring of the fuse status, allowing early detection of failures. The parking position and sealable closure option enhance safety during maintenance work. The frame terminal provides a robust and reliable connection for round conductors within the specified cross-section range. The power loss is a maximum of 26 W, with up to 9 W per fuse insert. Pollution degree 3 is suitable for environments with increased pollution risk, such as industrial plants with dust or dirt exposure.