Further information for Rittal 9363310 NH-fuse disconnect switch 3p 630 A
General
Model
for panel mounting
Material
Polyamide (PA 6), flammability rating according to UL 94, contact strips: electrolytic copper, silver-plated
Colour
RAL 9005, RAL 35745
Cable exit
Above/under
Electrical connection type
M10 screw
Fuse links
NH 3
Rated insulation voltage Ui
1.000 V
Rated operating voltage
690 V AC
For NH size
3
Test basis
IEC/DIN EN 60 947-3, DIN EN 60 269-2 (fuse inserts)
Width
250 mm
Height
298,5 mm
Depth
128,7 mm
Operating temperature range
-5 °C...35 °C
Storage temperature range
-25 °C...70 °C
Number of poles
3-pole
Pollution degree
3
Degree of protection IP according to IEC 60 529
IP 2XB
Fire load
44,94 MJ/m²
Maximum power dissipation
84 W
Copper content (kg/piece)
1,68
PCF/VE (Cradle-to-Gate)
25,87
For panel mounting
The Rittal RiLineX NH fuse switch disconnector type RX 9363310 is a 3-pole disconnector in size 3, specifically designed for mounting on mounting plates. It serves as a fuse switch disconnector in industrial electrical installations and enables the safe disconnection of circuits under operating voltage up to 690 V AC. The rated insulation voltage is 1,000 V, allowing application in high-voltage environments up to this limit. The disconnector is designed for use with NH fuse inserts of size 3 and features a screw connection design with M10 connectors, ensuring a secure and reliable connection for cables. The contact bars are made of electrolytic copper and are silver-plated to ensure high electrical conductivity and corrosion resistance.
Applications
The disconnector is suitable for use in industrial installations such as machine controls, distribution boxes, or drive systems, where a safe and visible disconnection of the power supply is required. Mounting on mounting plates allows flexible integration into existing control systems. The protection rating IP 2XB according to IEC 60 529 protects against finger contact and solid foreign objects, but not against splashing water or dust – thus it is intended for indoor installations. Pollution degree 3 accounts for environments with increased contamination risk, such as production halls or industrial processes.
Functions and Equipment in Detail
The disconnector's cover is lockable and sealable, preventing unauthorized manipulation and enhancing operational safety. Visual fuse monitoring allows the status of the installed NH fuse to be directly observed on the device without removing it. Integrated test points on the cover enable safe voltage testing without direct contact with the conductors. The park position of the cover facilitates maintenance work, as the cover can be held in a stable, open position without requiring additional holding devices.
Technology Explained Simply
The construction from polyamide (PA 6) with flame resistance according to UL 94 ensures high mechanical stability and fire resistance. The maximum power loss is 84 W, limiting thermal stress during operation. The operating temperature range is between -5 °C and 35 °C, while the storage temperature range from -25 °C to 70 °C allows storage under various conditions. Dimensions are 250 mm (width) × 298.5 mm (height) × 128.7 mm (depth), representing a compact design for mounting plates. Color variants RAL 9005 (black) and RAL 35745 (gray) allow optical harmonization with existing system components.
Compatibility and Accessories
The disconnector is designed for NH fuse inserts of size 3. Suitable accessories include the cover RX 9365533 for the connection space and the frame terminal RX 9365543, which is suitable for NH disconnectors of sizes 2 and 3. These components support safe and orderly installation and maintenance of the device.
Mounting and Installation
Mounting is done on mounting plates, with the disconnector's dimensions aligned to standard plate dimensions. Cable exit is possible at the top and bottom, ensuring flexible arrangement in the control system. The tool-free cable exit adjustment allows quick adaptation of the connection direction without additional tools.
Operational Advantages
The combination of a lockable cover, visual fuse monitoring, and integrated test points for voltage testing increases safety and efficiency during maintenance and inspection work. The park position reduces work effort during maintenance, as the cover can be held stably in the open position. The screw connection type M10 ensures a robust and reliable connection that remains stable even under high mechanical loads. The test basis IEC/DIN EN 60 947-3 and DIN EN 60 269-2 (for fuse inserts) ensures compliance with international standards for switching devices and fuses.