| General |
| Model | For 60 mm busbar systems |
| Material | Polyamide (PA 6), flammability rating according to UL 94, contact strips: electrolytic copper, silver-plated |
| Colour | RAL 9005, RAL 35745 |
| For rail systems with centre spacing | 60 mm |
| Cable exit | Above/under |
| Electrical connection type | Frame clamp |
| Fuse links | NH 3 |
| Rated operating voltage | 690 V AC |
| For NH size | 3 |
| Test basis | IEC/DIN EN 60 947-3, DIN EN 60 269-2 (fuse inserts) |
| Width | 250 mm |
| Height | 298,4 mm |
| Depth | 134,9 mm |
| Operating temperature range | -5 °C...35 °C |
| Storage temperature range | -25 °C...70 °C |
| Suitable for busbars | 15 x 5/10 mm, 20 x 5/10 mm, 30 x 5/10 mm |
| Suitable for busbar system | RiLineX, RiLine60 |
| Number of poles | 3-pole |
| Pollution degree | 3 |
| Degree of protection IP according to IEC 60 529 | IP 2XB |
| Fire load | 52,86 MJ/m² |
| Maximum power dissipation | 101 W |
| Copper content (kg/piece) | 2,255 |
| PCF/VE (Cradle-to-Gate) | 32,06 |
The Rittal RX 9362350 is an
NH fuse switch disconnector in size 3, specifically designed for 60 mm busbar systems. It serves as a
power disconnector in industrial electrical installations, where secure disconnection of power supply and integration of fuse inserts are required. The device is designed for use in enclosures and distributions connected to RiLineX or RiLine60 busbar systems, enabling reliable power disconnection and monitoring of fuse conditions.
Applications
The fuse switch disconnector is intended for industrial applications, particularly in machine building, manufacturing systems, and distribution systems, where high operational safety and serviceability are required. It is designed for a rated operational voltage of 690 V AC and is suitable for switchgear with pollution degree 3, indicating use in environments with increased risk of contamination. The protection rating IP 2XB protects against finger contact and solid foreign objects, but not against water or dust – thus it is intended for indoor use.
Functions and Equipment in Detail
The disconnector’s cover is
lockable and
sealable, enabling secure and documentable monitoring of operational status. A
visual fuse monitoring feature allows direct observation of the status of installed NH fuse inserts (size 3).
Secure voltage testing is performed via integrated test points on the cover, enabling testing without direct contact with live parts. A
parking position for the cover facilitates maintenance work, as the cover can be held in a stable, open position.
Technology Explained Simply
Electrical connection is made via a
frame terminal, designed for connecting round conductors with a cross-section of at least 120 mm² up to a maximum of 300 mm². The contact strips are made of
electrolytic copper, silver-plated, ensuring high conductivity and corrosion resistance. The housing is made of
polyamide (PA 6) with flame resistance according to UL 94, providing good fire resistance. The
cable exits are tool-free and individually convertible to top or bottom, enabling flexible installation on different busbar configurations.
Compatibility and Accessories
The disconnector is suitable for busbars with dimensions 15 x 5/10 mm, 20 x 5/10 mm, and 30 x 5/10 mm, and adapts to different busbar thicknesses without tools. It is designed for mounting on RiLineX and RiLine60 busbar systems. Available accessories include, among others, a
connection space cover for NH disconnector size 3 (RX 9365533), a
frame terminal 1=3 (RX 9365543), an
enclosure protection profile (RX 9365025),
mounting clips (RX 9365027), and a
microswitch (RX 9365505), which enhance installation and safety.
Mounting and Installation
Mounting is done directly onto the 60 mm busbar system. The tool-free conversion of the cable exit allows flexible adaptation to the specific installation. Fixing is achieved via integrated mounting points on the device. Dimensions are 250 mm (width) × 298.4 mm (height) × 134.9 mm (depth), with an operating temperature range of -5 °C to 35 °C. Storage temperature can vary between -25 °C and 70 °C.
Advantages in Operation
The disconnector provides high operational safety through integrated voltage testing and visual fuse monitoring. The parking position and sealable closure support maintenance and documentation. The use of silver-plated copper ensures long-term conductivity, while the polyamide housing offers high mechanical and thermal stability. Compatibility with various busbar thicknesses and tool-free conversion increase flexibility during installation.