| General |
| Model | For 60 mm busbar systems |
| Material | Polyamide (PA 6), flammability rating according to UL 94, contact strips: electrolytic copper, silver-plated |
| Colour | RAL 9005, RAL 35745 |
| For rail systems with centre spacing | 60 mm |
| Cable exit | Above/under |
| Electrical connection type | M10 screw |
| Fuse links | NH 2 |
| Rated operating voltage | 690 V AC |
| For NH size | 2 |
| Test basis | IEC/DIN EN 60 947-3, DIN EN 60 269-2 (fuse inserts) |
| Width | 208,5 mm |
| Height | 298,6 mm |
| Depth | 134,6 mm |
| Operating temperature range | -5 °C...35 °C |
| Storage temperature range | -25 °C...70 °C |
| Suitable for busbars | 15 x 5/10 mm, 20 x 5/10 mm, 30 x 5/10 mm |
| Suitable for busbar system | RiLineX, RiLine60 |
| Number of poles | 3-pole |
| Pollution degree | 3 |
| Degree of protection IP according to IEC 60 529 | IP 2XB |
| Fire load | 46,16 MJ/m² |
| Maximum power dissipation | 98 W |
| Copper content (kg/piece) | 1,75 |
| PCF/VE (Cradle-to-Gate) | 26,35 |
The Rittal RX 9362210 is an
NH fuse switch disconnector in size 2, specifically designed for 60 mm busbar systems. It serves as a switching and disconnecting device in industrial electrical installations, where secure disconnection and visual monitoring of the fuse are required. The device is designed for use in switchgear with a rated operational voltage of 690 V AC and features a 3-pole configuration. The construction allows for direct mounting on RiLineX or RiLine60 busbar systems with a center-to-center spacing of 60 mm, accommodating busbar thicknesses of 15 x 5/10 mm, 20 x 5/10 mm, and 30 x 5/10 mm.
Applications
This fuse switch disconnector is intended for industrial applications in switchgear, distribution boxes, and machine controls, where reliable disconnection of power supply and visual inspection of the fuse status are necessary. It is particularly suitable for installations tested according to IEC/DIN EN 60 947-3 and DIN EN 60 269-2 (fuse inserts). The protection rating IP 2XB ensures protection against finger contact and solid foreign objects, although the device is not designed for outdoor use or in damp environments.
Functions and Equipment in Detail
The disconnector’s cover is
lockable and
sealable, enabling secure and documentable disconnection.
Visual fuse monitoring allows the status of the installed NH fuse (size 2) to be directly observed on the device.
Secure voltage testing is performed via integrated test points on the cover, enabling inspection without direct access to the contacts. An integrated
parking position system facilitates maintenance work, as the cover can be held in a stable, open position. The
cable exit can be toollessly reconfigured between top and bottom, allowing flexible installation at various locations within the enclosure.
Technology Explained Simply
The electrical connection is made via a
screw connection M10, suitable for connecting cables. The contact strips are made of
electrolytic copper, silver-plated, ensuring high electrical conductivity and corrosion resistance. The housing is made of
polyamide (PA 6), which meets UL 94 flammability requirements. The operating temperature range is between -5 °C and 35 °C, while the storage temperature range extends from -25 °C to 70 °C. The maximum power loss is 98 W, indicating the thermal load during operation. Pollution degree 3 indicates that the device is designed for environments with increased risk of contamination.
Compatibility and Accessories
The disconnector is compatible with RiLineX and RiLine60 busbar systems. Various accessories are available to extend functionality: The
frame terminal RX 9365543 serves as a connection terminal for NH disconnectors in sizes 2 and 3. The
enclosure protection profile RX 9365025 (length 1200 mm) and the
mounting clip RX 9365027 enable secure mounting and covering. The
microswitch RX 9365505 can be used to signal the disconnector’s status, and the
connection space cover RX 9365532 protects the connection area.
Mounting and Installation
Mounting is done directly onto the 60 mm busbar system. The tool-free reconfiguration of the cable exit allows flexible installation without additional tools. Dimensions are 208.5 mm (width) × 298.6 mm (height) × 134.6 mm (depth). Installation requires no additional components, as the device is designed for direct mounting.
Operational Advantages
The disconnector provides high operational safety through its lockable and sealable cover and visual fuse monitoring. The integrated test points for voltage testing increase safety during maintenance. The parking position simplifies work on the device, and the tool-free reconfiguration of the cable exit reduces installation time. The use of polyamide and silver-plated copper ensures long service life and high reliability in industrial applications.