| General |
| Model | For 60 mm busbar systems |
| Size | 1 |
| Material | Polyamide (PA 6), flammability rating according to UL 94, contact strips: electrolytic copper, silver-plated |
| System width | 60 mm busbar system |
| Colour | RAL 9005, RAL 35745 |
| Cover | lockable, sealable |
| For rail systems with centre spacing | 60 mm |
| Fuse monitoring | visual |
| Cable exit | individually convertible (top/bottom) |
| Voltage testing | Integrated test points on the cover |
| Connection | Screw connection size M10 |
| Electrical connection type | M10 screw |
| Fuse links | NH 1 |
| Number of poles | 3-pole |
| Rated operating voltage | 690 V AC |
| For NH size | 1 |
| Nominal current | 250 A |
| Test basis | IEC/DIN EN 60 947-3, DIN EN 60 269-2 (fuse inserts) |
| Width | 181,5 mm |
| Height | 298 mm |
| Depth | 116,7 mm |
| Operating temperature range | -5 °C...35 °C |
| Storage temperature range | -25 °C...70 °C |
| Suitable for busbars | 15 x 5/10 mm, 20 x 5/10 mm, 30 x 5/10 mm |
| Suitable for busbar system | RiLineX, RiLine60 |
| Utility category | AC-23B (400 V/100 A), AC-22B (500 V/100 A), AC-21B (690 V/100 A), DC-22B (250 V/100 A), DC-21B (440 V/100 A) |
| Pollution degree | 3 |
| Degree of protection IP according to IEC 60 529 | IP 2XB |
| Fire load | 36,19 MJ/m² |
| Maximum power dissipation | 51 W |
| Power loss per fuse element (max.) | 23 W |
| Copper content (kg/piece) | 0,8 |
| PCF/VE (Cradle-to-Gate) | 15,39 |
The RiLineX NH fuse-disconnector in size 1 from Rittal is specifically designed for 60 mm busbar systems and provides reliable disconnection and protection functions in industrial electrical installations. With a
lockable and sealable cover, it ensures a high safety standard and prevents unauthorized access. The
visual fuse monitoring allows for quick status overview of the installed NH fuse, making maintenance and inspection work more efficient. The integrated
test points on the cover enable safe voltage testing, which is essential for complying with safety regulations and carrying out maintenance work. The
parking position facilitates maintenance, as the disconnector can be fixed in a safe, non-conductive position. The connection is made via
screw connection size M10, ensuring a stable and secure connection to cables and wiring. The
individually convertible cable exit (top or bottom) offers flexibility during installation and adapts to different arrangements in the enclosure.