| General |
| Model | Universal |
| Material | Polyamide (PA 6), flammability according to UL 94 |
| Colour | RAL 9005, RAL 35745 |
| Scope of delivery | Including 3 connection chamber covers, 2 traverses and mounting material |
| Degree of protection IP according to IEC 60 529 | IP 2XB |
| Rated impulse voltage Uimp | 8 kV |
| Rated voltage | 690 V AC, 600 V AC (UL) |
| Rated insulation voltage Ui | at rail thickness 5 mm: 800 V, at rail thickness 10 mm: 1,000 V |
| Pollution degree | 3 |
| Number of poles | 3-pole |
| Cable exit | Above/under |
| Electrical connection type | M10 screw |
| Cross section | 29 mm², 10 mm² |
| Suitable for manufacturer (type) | Easily find the appropriate device adapter using our selection guide in the Downloads section. |
| Suitable for busbar system | RiLineX, RiLine60 |
| Maximum power dissipation | 19,5 W |
| Frequency of fundamental wave | 50...60 Hz |
| Humidity (non-condensing) | 10...90 % |
| Suitable for busbars | 15 x 5/10 mm, 20 x 5/10 mm, 30 x 5/10 mm |
| Operating temperature range | -25 °C...55 °C |
| Storage temperature range | -25 °C...75 °C |
| Width | 145 mm |
| Height | 325,8 mm |
| Depth | 76,4 mm |
| Fire load | 16,043 MJ/m² |
| Copper content (kg/piece) | 1,652 |
| PCF/VE (Cradle-to-Gate) | 21,11 |
The Rittal RX 9360625 is a
CB-device adapter for 60 mm busbar systems, specifically designed for use in industrial enclosures. As a
universal version with sliding nuts, it enables flexible mounting of compact circuit breakers (MCCB) and offers a tool-free push-on mounting. The adapter is rated for a maximum nominal current of 400 A and supports mounting on RiLineX and RiLine60 busbar systems.
Applications
The adapter is used for direct mounting of compact circuit breakers onto the board and enables quick and easy pre-assembly of market-standard switch types outside the enclosure. This reduces mounting time within the enclosure and increases installation efficiency. It is suitable for industrial applications requiring flexible and reliable power distribution, particularly in enclosures with 60 mm wide busbars.
Functions and Equipment in Detail
The adapter features a
tool-free push-on mounting, which is possible up to 250 A, with busbar thickness adjustable between 5 mm and 10 mm via semi-automatic adjustment. The
connection type is via M10 screws, supporting a cross-section of 29 mm² (for 5 mm busbar thickness) and 10 mm² (for 10 mm busbar thickness). The
cable exit can be easily reconfigured from top to bottom or vice versa, providing high flexibility during installation.
Technology Explained Simply
The adapter is made of
polyamide (PA 6), which according to UL 94 exhibits a specific flammability rating, important for safety in electrical installations. The
protection rating IP 2XB according to IEC 60 529 protects against finger contact and solid foreign objects, but not against water or dust. The
rated voltage is 690 V AC (600 V AC according to UL), and the
rated insulation voltage Ui is 800 V for 5 mm and 1,000 V for 10 mm busbar thickness. The
rated impulse voltage Uimp is 8 kV, describing the device’s ability to withstand electrical overvoltages. The
pollution degree 3 is intended for environments with increased contamination, as commonly found in industrial facilities.
Compatibility and Accessories
The adapter is compatible with the busbar systems
RiLineX and
RiLine60 and adapts to busbars with dimensions 15 x 5/10 mm, 20 x 5/10 mm, and 30 x 5/10 mm. As accessories, the
enclosure protection profile RX 9365025 (length 1200 mm) and the
mounting clip RX 9365027 are available, which can be used for secure mounting and protection of connections.
Mounting and Installation
Mounting is done tool-free by pushing the adapter onto the busbar. The sliding nuts allow easy adjustment of the fastening to various switch types. The delivery includes
3 connection space covers, 2 cross-braces, and mounting material, which facilitates direct installation in the enclosure. The
operating temperature range is between -25 °C and +55 °C, while the
storage temperature range extends from -25 °C to +75 °C. The operating humidity must not be condensing and ranges between 10 % and 90 %.
Advantages in Operation
The adapter offers high mounting flexibility, reduces installation time through pre-assembly outside the enclosure, and ensures safe and reliable power distribution. The tool-free mounting and easy adjustment of busbar thickness increase efficiency during commissioning. The power loss is a maximum of 19.5 W, which is relevant for the thermal load on the enclosure. The frequency of the fundamental wave is 50 to 60 Hz, matching standard mains frequencies. The
copper content is 1.652 kg per piece, indicating the material composition.