| General |
| Material | Polyamide (PA 6), flammability rating according to UL 94, E-Cu |
| Colour | RAL 35745, RAL 9005 |
| Scope of delivery | Including integrated busbars |
| Degree of protection IP according to IEC 60 529 | IP 2XB |
| Standards | IEC 61 439-1/-2, UL 508 |
| Rated current max. | 550 A |
| Rated current (UL) | 540 A |
| Electrical values UL (SCCR) | 45 kA - 600 V, RMS, unprotected, 100 kA - 600 V, Fuse Class L max. 1600 A, JDDZ/7, 100 kA - 600 V, Circuit Breaker max. 600 A, DIVQ/7, 100 kA - 480 V, Circuit Breaker max. 800 A, DIVQ/7, 65 kA - 600 V, Circuit Breaker max. 800 A, DIVQ/7 |
| Center-to-center spacing of busbars | 60 mm |
| Rated impulse voltage Uimp | 12 kV |
| Rated voltage | 1.000 V AC, 1.500 V DC, 600 V AC (UL), 600 V DC (UL) |
| Rated insulation voltage Ui | 1.000 V AC, 1.500 V DC |
| Rated surge withstand current Ipk | 115,5 kA, 94,5 kA (UL) |
| Rated short-time withstand current / t | 45 kA/500 ms |
| Over voltage category | 4 |
| Pollution degree | 3 |
| Busbar dimensions | 30 mm x 5 mm |
| Number of poles | 3-pole |
| Frequency of fundamental wave | 50...60 Hz |
| Humidity (non-condensing) | 10...90 % |
| Operating temperature range | -5 °C...55 °C |
| Storage temperature range | -25 °C...75 °C |
| Width | 1.105 mm |
| Height | 246 mm |
| Depth | 49,2 mm |
| Fire load | 115,574 MJ/m² |
| Copper content (kg/piece) | 4,419 |
| PCF/VE (Cradle-to-Gate) | 62,17 |
The Rittal RiLineX complete board type RX 9360024 is a
3-pole power distribution board with a
rated current of 550 A, specifically designed for use in industrial enclosures. It is designed for enclosures with a width of 1200 mm and has a length of 1105 mm. The board is made of
polyamide (PA 6), classified as UL 94 E-Cu, ensuring high flame retardancy. The integrated
busbars have dimensions of
30 mm x 5 mm and are arranged with a
center-to-center spacing of 60 mm. The delivery includes the
pre-assembled board including the busbars, reducing installation time and enabling quick commissioning.
Applications
The RiLineX board is suitable for applications in the range of
alternating current up to 1000 V AC and
direct current up to 1500 V DC. It is used in industrial electrical installations where reliable power distribution with high short-circuit withstand capability is required. The
overvoltage category 4 and
pollution degree 3 make it suitable for environments with high electrical loads and pollution risks. The operating temperature ranges from
-5 °C to 55 °C, and the storage temperature ranges from
-25 °C to 75 °C.
Functions and Equipment in Detail
The board provides complete
touch protection class up to IP 2XB according to IEC 60 529. By using cover strips (e.g. RX 9365020), an upgrade to
IP 3X is possible. Cable routing at the rear of the board enables flexible system design, especially for control wiring. The
baying of multiple boards is achieved using RiLineX baying connectors (e.g. RX 9360000), without impairing short-circuit withstand capability. The
fully digital product data supports planning and documentation, resulting in time savings.
Technology Explained Simply
The
rated short-time withstand current is 45 kA/500 ms, meaning the board can safely withstand short-term current surges up to this value. The
rated impulse voltage Uimp is 12 kV, ensuring insulation capability against electrical overvoltages. The
rated insulation voltage Ui is 1000 V AC and 1500 V DC, ensuring electrical safety at high voltages. The
rated impulse current Ipk is 115.5 kA (115.5 kA according to UL), describing the board’s ability to withstand high current surges for a short period. The
rated voltage includes 1000 V AC, 1500 V DC (IEC) as well as 600 V AC and 600 V DC (UL). The
frequency of the fundamental wave is 50 to 60 Hz.
Compatibility and Accessories
The board is certified to
IEC 61 439-1/-2 and
UL 508, confirming compliance with international safety and quality standards. It can be mounted
horizontally, vertically, and overhead, enabling flexible installation in various enclosure configurations. Compatible accessories include
cover strips RX 9365020 to increase touch protection class and
baying set RX 9360000 for connecting multiple boards.
Mounting and Installation
Mounting is done by direct fixation in the enclosure. The pre-assembled construction with integrated busbars reduces installation time. Cable routing at the rear enables clean and structured wiring. Baying is done using special connectors that maintain electrical safety and short-circuit withstand capability.
Operational Advantages
The RiLineX board offers
high electrical safety through tested short-circuit withstand capability and touch protection. The
digital product documentation supports planning and maintenance. The
expandable system architecture allows flexible adaptation to growing requirements. The
certification according to IEC and UL ensures use in international markets. The
combination of robust material and precise construction ensures long service life and reliable performance in industrial environments.