| General |
| Model | PDU, managed |
| Material | Aluminium profile, black anodised, mounting slots: plastic |
| Scope of delivery | Including mounting hardware |
| Options | Overvoltage protection Type 3 with replaceable diverters during operation, with status monitoring, integrable in PDU housing, differential current measurement (Type B) per input/phase/fuse, monitoring of optional overvoltage protection, CMC III CAN-Bus sensors for environment monitoring connectable, max. 16 sensors, other housing colours available |
| Width | 44 mm |
| Depth | 70 mm |
| Length | 1.695 mm |
| Number of sockets and type | 42 x C13 |
| Socket outlets | 42 x C 13 |
| Rated operating voltage | 400 V (AC) |
| Rated current (max.) | 16 A |
| Nominal power | 11 kW |
| Power supplies | Number: 1, phases per input: 3~ |
| Connection cable length | 3 m |
| Electrical connection type | CEE |
| Interfaces | USB 2.0 port (USB-A) for mass configuration, firmware update & data logging, CAN-Bus interface (RJ45) for max. 16 environment sensors, serial interface RS232 (RJ12) for LTE unit, scripting, CLI, use of own certificates/TLS 1.2, email sending on alarm (SMTP), user management including rights management, LDAP(S)/Radius/Active Directory integration, Syslog server integration (max. 2 servers), fully redundant Ethernet interface 10/100/1000 Mbit/s |
| Policies | EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU |
| Standards | EN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, EN 62053-21 |
| Protocols | Web server (HTTP, HTTPS, SSL) SSH, Telnet, NTP, TCP/IP v4 & v6, DHCP, DNS, SNMP v1, v2c & v3, Modbus/TCP, OPC-UA, MIB for integration into 3rd party DCIM software, FTP/SFTP (update/file transfer) |
| Operating temperature range | 5 °C...50 °C |
| Humidity (non-condensing) | 10...95 % |
| Storage temperature range | -20 °C...70 °C |
| Suitable for | Housing type: VX IT cabinet frame: ≥ 1,800 mm, housing type: VX IT 19"-profile rails: ≥ 2,000 mm |
The Rittal DK 7979442 is a
managed PDU (Power Distribution Unit) for use in IT network and server racks. It provides distributed power supply and comprehensive energy measurement and monitoring functions for each individual outlet socket. The power distribution is designed for use in 19-inch technology and is particularly suitable for racks of type VX IT with a minimum length of 1,800 mm for the cabinet frame or 2,000 mm for the 48,3 cm ( 19 inch ) profile rails. The PDU is mounted tool-free in Zero-U-Space, minimizing space requirements in the rack.
Applications
The PDU is designed for use in data centers, server rooms, and IT infrastructures where precise energy management, load monitoring, and remote control are required. It enables central control and monitoring of power consumption, voltage, current, and power per socket. The integrated real-time clock with battery backup (max. 10 years, replaceable) ensures continuity of time data even during power failure. The PDU is designed for an operating temperature of 5 °C to 50 °C and humidity of 10 % to 95 % (non-condensing).
Functions and Equipment in Detail
The PDU features 42 sockets of type
C13 (IEC 60320), each of which can be individually monitored and controlled. The rated operating voltage is 400 V (AC), the maximum rated current is 16 A, corresponding to a rated power of 11 kW. Power input is via a CEE plug with a 3 m long supply cable. The PDU is self-powered, without external power supply. Measurement accuracy is ±1 % (kWh) according to standard
EN 62053-21.
The sockets are color-coded: L1 (pink), L2 (black), L3 (white), to visually distinguish phases and fuse circuits. The integrated control unit with a bright TFT display (128x128 pixels, RGB, with backlight) shows performance data and basic configuration. The display is rotatable by 180° and replaceable. Multicolored LEDs (green/yellow/red) indicate the switching status and thresholds per socket. An integrated electromagnetic buzzer provides acoustic alarm.
Technology Explained Simply
The PDU is equipped with a powerful CPU (ARM Cortex A8) enabling processing of measurement data and control of functions. The PDU is redundantly powered across all phases, ensuring fault-tolerant operation. The relays are bistable, allowing low power consumption and high switching capacity even at high inrush currents (up to max. 300 A). Switching functions include programmable on/off behavior after voltage recovery (on/off/last status) and programmable switching behavior (time/programmable logic). Relay states are stored even during power failure.
Compatibility and Accessories
The PDU is equipped with a variety of interfaces: a fully redundant Ethernet interface (10/100/1000 Mbit/s), a USB 2.0 port (USB-A) for mass configuration, firmware updates, and data logging, a CAN-Bus interface (RJ45) for up to 16 environmental sensors of type CMC III, and a serial interface RS232 (RJ12) for LTE unit, scripting, and CLI. Communication occurs via protocols such as HTTP/HTTPS, SSH, Telnet, NTP, TCP/IP v4 & v6, DHCP, DNS, SNMP v1, v2c & v3, Modbus/TCP, OPC-UA, and FTP/SFTP. Integration into DCIM software is possible via MIB.
Additionally, optional features include surge protection Type 3 with replaceable discharge elements during operation and status monitoring, differential current measurement (Type B) per input/phase/fuse, and monitoring of optional surge protection. Connection to LDAP(S), Radius, or Active Directory, as well as to Syslog servers (max. 2 servers), is possible. E-mail alarms can be sent via SMTP.
Mounting and Installation
Mounting is tool-free in the Zero-U-Space of VX IT or TS IT racks. The delivery includes the required mounting material. The PDU is designed for vertical mounting and can be installed in racks with a minimum length of 1,800 mm (cabinet frame) or 2,000 mm (48,3 cm ( 19 inch ) profile rails). Dimensions are 44 mm (width) × 1,695 mm (length) × 70 mm (depth).
Operational Advantages
The PDU enables precise energy management with individual control and monitoring per socket. The integrated real-time clock and storage of relay states ensure reliable operational continuity. Redundant power supply and bistable relays increase operational safety. Support for protocols such as SNMP, Modbus/TCP, and OPC-UA facilitates integration into existing monitoring and management systems. The ability to set individual thresholds for voltage, current, and power per socket enables flexible and safe use.
The PDU complies with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU. Standards EN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, and EN 62053-21 are met. The PDU is suitable for use in IT infrastructures with high requirements for reliability and energy efficiency.
Batteries are not included in the delivery scope.