| General |
| Model | PDU, managed |
| Material | Aluminium profile, black anodised, mounting slots: plastic |
| Scope of delivery | Including mounting hardware |
| Options | Overvoltage protection Type 3 with replaceable diverters during operation, with status monitoring, integrable in PDU housing, differential current measurement (Type B) per input/phase/fuse, monitoring of optional overvoltage protection, CMC III CAN-Bus sensors for environment monitoring connectable, max. 16 sensors, other housing colours available |
| Width | 44 mm |
| Depth | 70 mm |
| Length | 1.095 mm |
| Number of sockets and type | 18 x C13 / 3 x C19 |
| Socket outlets | 18 x C 13, 3 x C 19 |
| Rated operating voltage | 400 V (AC) |
| Rated current (max.) | 16 A |
| Nominal power | 11 kW |
| Power supplies | Number: 1, phases per input: 3~ |
| Connection cable length | 3 m |
| Electrical connection type | CEE |
| Interfaces | USB 2.0 port (USB-A) for mass configuration, firmware update & data logging, CAN-Bus interface (RJ45) for max. 16 environment sensors, serial interface RS232 (RJ12) for LTE unit, scripting, CLI, use of own certificates/TLS 1.2, email sending on alarm (SMTP), user management including rights management, LDAP(S)/Radius/Active Directory integration, Syslog server integration (max. 2 servers), fully redundant Ethernet interface 10/100/1000 Mbit/s |
| Policies | EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU |
| Standards | EN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, EN 62053-21 |
| Protocols | Web server (HTTP, HTTPS, SSL) SSH, Telnet, NTP, TCP/IP v4 & v6, DHCP, DNS, SNMP v1, v2c & v3, Modbus/TCP, OPC-UA, MIB for integration into 3rd party DCIM software, FTP/SFTP (update/file transfer) |
| Operating temperature range | 5 °C...50 °C |
| Humidity (non-condensing) | 10...95 % |
| Storage temperature range | -20 °C...70 °C |
| Suitable for | Housing type: VX IT cabinet frame: ≥ 1,200 mm, housing type: VX IT 19"-profile rails: ≥ 1,800 mm |
The Rittal DK 7979435 is a
managed PDU (Power Distribution Unit) for use in IT network and server racks. It serves as a high-end power distribution unit with integrated energy measurement and monitoring functions, available for each output socket. The device is designed for use in 19-inch technology and offers a compact form factor with a width of 44 mm, depth of 70 mm, and length of 1,095 mm. The PDU is rated for an operating voltage of 400 V (AC) and features a nominal current of 16 A and a nominal power of 11 kW. Power supply is via a CEE plug with a 3 m long supply cable.
Applications
The PDU is specifically designed for use in IT infrastructures, particularly in racks of the Rittal VX IT or TS IT type. When mounted vertically, it can be installed tool-free in Zero-U-Space, minimizing rack space requirements. The installation solution is suitable for enclosure frames with a minimum length of 1,200 mm and for 48,3 cm ( 19 inch ) profile rails with a minimum length of 1,800 mm. The phase color coding (L1=pink, L2=black, L3=white) supports assignment and maintenance.
Functions and Equipment in Detail
The PDU features 18 C13 and 3 C19 sockets made of plastic. The sockets are equipped with multicolored LEDs (green/yellow/red) that visually indicate the switching status and limits for each output. A bright TFT display with 128x128 pixels (RGB) and backlighting shows power data and basic configuration. The display is rotatable by 180° and replaceable, ensuring optimal visibility in various mounting positions. The PDU is self-powered, so no external power supply is required.
Technology Explained Simply
The PDU is equipped with an integrated, fully redundant power supply unit that can be powered from all phases. This ensures fault-tolerant power supply. Measurement accuracy is ±1 % (kWh) according to EN 62053-21. Energy measurement is performed per phase, per input, and per output socket. Additionally, voltage, current, frequency, active power, apparent power, power factor (cosPhi), phase angle, and neutral conductor current are measured. Fuse monitoring is available for PDUs with integrated fuses. The PDU includes an integrated real-time clock with battery backup (up to 10 years, replaceable), which retains time information even during power failure.
Compatibility and Accessories
The PDU supports connection to CMC III CAN-Bus sensors for environmental monitoring, with up to 16 sensors connectable. Optionally, a Type 3 surge protection device with replaceable discharge elements during operation and status monitoring can be integrated. Differential current measurement (Type B) is available per input, phase, and fuse. Accessories include CAN-Bus cables in various lengths (0.5 m, 1.0 m, 1.5 m), covers for C13 and C19 sockets, mounting adapters, and a numeric code lock for CMC III. The PDU is equipped with an integrated electromagnetic buzzer that triggers acoustic alarms.
Mounting and Installation
Mounting is tool-free in Rittal VX IT or TS IT racks. The delivery includes mounting hardware. The PDU can be mounted vertically in Zero-U-Space, minimizing rack space requirements. Installation is performed via the CEE plug at the input.
Operational Advantages
The PDU offers programmable power-on behavior after voltage recovery (on/off/last status) and programmable switching behavior (time/programmable logic). Relay states are retained even during power failure. The bistable relays have low power consumption and high switching capacity, enabling coverage of higher inrush currents up to max. 300 A. Grouping allows simultaneous switching of multiple outputs. Emergency power supply for the web server is provided via PoE, ensuring sequential shutdown of outputs during power failure. The PDU has low self-consumption and is therefore designed to be energy-efficient.
Interfaces and Protocols
The PDU features a fully redundant Ethernet interface (10/100/1000 Mbit/s), a USB 2.0 port (USB-A) for mass configuration, firmware updates, and data logging, a CAN-Bus interface (RJ45) for environmental sensors, and a serial interface RS232 (RJ12) for LTE unit, scripting, and CLI. Communication occurs via protocols such as HTTP, HTTPS, SSL, SSH, Telnet, NTP, TCP/IP v4 & v6, DHCP, DNS, SNMP v1, v2c & v3, Modbus/TCP, OPC-UA, and FTP/SFTP. Integration into 3rd-party DCIM software is possible via MIB. User management includes rights management, LDAP(S)/Radius/Active Directory integration, and Syslog server integration (up to 2 servers). Email notification on alarm (SMTP) is also supported. The operating temperature ranges from 5 °C to 50 °C, and relative humidity (non-condensing) from 10 % to 95 %. Storage temperature is from -20 °C to 70 °C. The PDU complies with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU. Standards EN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, and EN 62053-21 are met.