Rittal 7979242, EAN: 4028177947818

Rittal 7979242 PDU Metered 16A/3P CEE 42xC13

19 Inch-Technology > Accessories/Equipment > Energy Management

Rittal 7979242 PDU Metered 16A/3P CEE 42xC13

Lieske Part No. 593561
Mfg Part No 7979242
EAN-Code 4028177947818
Manufacturer Rittal
Here only 871,59 EUR
1.037,19 EUR incl. VAT

Further information for Rittal 7979242 PDU Metered 16A/3P CEE 42xC13

General
ModelPDU, metered
MaterialAluminium profile, black anodised, mounting slots: plastic
Scope of deliveryIncluding mounting hardware
OptionsOvervoltage protection Type 3 with replaceable diverters during operation, with status monitoring, integrable in PDU housing, differential current measurement (Type B) per input/phase/fuse, monitoring of optional overvoltage protection, CMC III CAN-Bus sensors for environment monitoring connectable, max. 16 sensors, other housing colours available
Description of measurement functionsmeasurement per phase or input, powerful CPU (ARM Cortex A8), digital input (potential-free contact), additional alarm output/relay output (changeover contact)
Width44 mm
Depth70 mm
Length1.695 mm
Number of sockets and type42 x C13
Rated operating voltage400 V (AC)
Rated current (max.)16 A
Nominal power11 kW
Power suppliesNumber: 1, phases per input: 3~
Connection cable length3 m
Electrical connection typeCEE
InterfacesUSB 2.0 port (USB-A) for mass configuration, firmware update & data logging, CAN-Bus interface (RJ45) for max. 16 environment sensors, serial interface RS232 (RJ12) for LTE unit, scripting, CLI, use of own certificates/TLS 1.2, email sending on alarm (SMTP), user management including rights management, LDAP(S)/Radius/Active Directory integration, Syslog server integration (max. 2 servers), fully redundant Ethernet interface 10/100/1000 Mbit/s
PoliciesEMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU
StandardsEN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, EN 62053-21
ProtocolsWeb server (HTTP, HTTPS, SSL) SSH, Telnet, NTP, TCP/IP v4 & v6, DHCP, DNS, SNMP v1, v2c & v3, Modbus/TCP, OPC-UA, MIB for integration into 3rd party DCIM software, FTP/SFTP (update/file transfer)
Operating temperature range5 °C...50 °C
Humidity (non-condensing)10...95 %
Storage temperature range-20 °C...70 °C
Suitable forHousing type: VX IT cabinet frame: ≥ 1,800 mm, housing type: VX IT 19"-profile rails: ≥ 2,000 mm
The Rittal DK 7979242 is a PDU (Power Distribution Unit) with integrated energy measurement, specifically designed for use in IT network and server racks. As a metered model, it enables precise measurement of power consumption values per phase or input, allowing the energy demand of an entire rack to be monitored. The device features a compact design with a width of 44 mm, a length of 1,695 mm, and a depth of 70 mm, making it suitable for installation in standard 19-inch racks. The power distribution is equipped with 42 sockets of type C13, made of plastic, suitable for connecting IT devices. The entire construction consists of an aluminium profile, black anodized, ensuring a robust and durable structure.

Applications

The PDU is designed for use in IT infrastructures, particularly in server and network racks, where precise energy monitoring and distribution are required. It is especially suitable for racks with a minimum length of 1,800 mm (for VX IT cabinet frames) or 2,000 mm (for VX IT 19-inch profile rails). Vertical mounting is tool-free in Zero-U-Space, simplifying installation in existing racks. The phase colour coding (L1=pink, L2=black, L3=white) facilitates assignment and maintenance.

Functions and Equipment in Detail

The PDU features an integrated, fully redundant power supply fed from all phases, ensuring fault-tolerant and reliable operation. Measurement accuracy is ±1 % (kWh) according to the standard EN 62053-21, ensuring high reliability in energy measurement. Measurement functions include voltage, current, frequency, active power, active energy, apparent power, apparent energy, power factor (cosPhi), phase angle, and neutral conductor current measurement for unbalanced load detection. Additionally, fuse monitoring is integrated if the PDU is equipped with an integrated fuse.

Technology Explained Simply

Control is managed by a powerful CPU based on an ARM Cortex A8 processor, responsible for processing measurement data and communication via various interfaces. A bright TFT display with 128x128 pixels (RGB) and backlighting shows performance data and basic configuration. The display is rotatable by 180° and replaceable, allowing adaptation to different mounting positions. An integrated real-time clock with battery backup (max. 10 years, replaceable) ensures correct time display even during power failure. An integrated electromagnetic buzzer enables acoustic alarm triggering when preset thresholds are exceeded.

Compatibility and Accessories

The PDU is equipped with a variety of interfaces, including a fully redundant Ethernet interface (10/100/1000 Mbit/s), a USB 2.0 interface (USB-A) for firmware updates and data logging, a CAN-Bus interface (RJ45) for connecting up to 16 environmental sensors of type CMC III, and a serial RS232 interface (RJ12). Communication occurs via protocols such as HTTP/HTTPS, SSH, Telnet, SNMP v1/v2c/v3, Modbus/TCP, OPC-UA, FTP/SFTP, NTP, TCP/IP v4 & v6, DHCP, DNS, and MIB, enabling integration into DCIM software and other monitoring systems. The PDU also supports connection to LDAP(S), Radius, Active Directory, and Syslog servers (up to 2 servers). Email alerts can be sent via SMTP. Optionally, a surge protection Type 3 with replaceable discharge elements during operation can be integrated and monitored. A differential current measurement (Type B) per input, phase, or fuse is also available.

t
Mounting and Installation

Mounting is tool-free in Zero-U-Space of Rittal VX IT- or TS IT-racks. The delivery includes the mounting hardware required for installation. The supply cable has a length of 3 m and is fitted with a CEE plug. The rated operating voltage is 400 V (AC), the rated current max. 16 A, corresponding to a rated power of 11 kW. The operating temperature ranges from 5 °C to 50 °C, and the relative humidity (non-condensing) from 10 % to 95 %. The storage temperature is -20 °C to 70 °C.

Operational Advantages

The PDU features an energy-efficient design with low self-consumption. The integrated real-time clock with battery backup ensures continuity of time display. Adjustable thresholds for voltage, current, and power allow for individual alarm configuration. An operating hour counter (total and cyclic, resettable) supports maintenance planning. Support for CMC III sensors enables monitoring of environmental conditions such as temperature and humidity. The PDU is self-powered and does not require an external power supply. The integrated, fully redundant power supply increases system reliability.

Standards and Regulations

The PDU complies with the EMC Directive 2014/30/EU and the Low Voltage Directive 2014/35/EU. Standards EN 62368-1, EN 61000-3, EN 61000-4, EN 61000-6, EN 62053-21 are met, ensuring safety and functionality during operation.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/593561
qrcode für Rittal 7979242 PDU Metered 16A/3P CEE 42xC13