Rittal 7030262, EAN: 4028177925861

Rittal 7030262 sight door VX IT with emergency ventilation

Cables > Data lines > Cat6 Patch Cable

Rittal 7030262 sight door VX IT with emergency ventilation

Lieske Part No. 593705
Mfg Part No 7030262
EAN-Code 4028177925861
Manufacturer Rittal
Here only 1.478,44 EUR
1.759,34 EUR incl. VAT

Further information for Rittal 7030262 sight door VX IT with emergency ventilation

General
ModelVision windows: single-pane safety glass, tinted, spring dampers for flap opening, magnets for securing flaps, flaps open in de-energised state, vision door: 2x single-pane safety glass, tinted, single-piece, with ventilation flaps, frame: aluminium extruded profile
Technical dataVentilation flap construction outward: 200 mm (in open position), Mechanism construction inward: 52.5 mm, Door hinge: right (for single doors, hinge position changeable from right to left), Cable connection from door hinge: 2.5 m
Function principleControlled via CMC III Door Control Module (DCM), Integrated vertical ventilation flaps open automatically in emergency – in case of cooling system failure or activation of fire suppression system – air in the room is used for emergency cooling depending on room volume and temperature, or fire suppressant gas can directly enter IT cabinets, Front and rear doors of the ADO system must always be used
MaterialFrame: aluminium extruded profile, vision panels: single-pane safety glass, tinted
Scope of deliveryVision door with comfort handle for profile half-cylinder with security locking 3524 E
At DC0,78 A
Width600 mm
Height2.000 mm
Degree of protection IP according to IEC 60 529IP 20 with closed ventilation flaps
The Rittal VX 7030262 is an aluminium viewing door for the VX IT enclosure system, specifically designed for the Automatic Door Opening (ADO) system. It replaces the standard door and enables automatic opening of the integrated ventilation flaps in an emergency, for example, in case of power failure or activation of a fire suppression system. The door is manufactured with a width of 600 mm and a height of 2,000 mm and features two single-pane safety glass viewing panels, which are tinted. The frame material consists of aluminium extruded profile, ensuring high stability and durability.

Applications
The viewing door is intended for use in IT enclosures, particularly in environments where emergency cooling or direct supply of fire suppressant gas into the enclosure is required. The automatic opening of the ventilation flaps during power failure or alarm condition enables efficient use of room air for cooling or direct supply of fire suppressant gas. The door is designed for indoor use and meets protection class IP 20 with closed ventilation flaps.

Functions and Equipment in Detail
The integrated vertical ventilation flaps open automatically in an emergency when the power supply fails or an alarm is triggered. The flaps are held closed by six electric magnets and open in the de-energized state. The opening is facilitated by six spring dampers, which open the flaps gently and controlled. Additionally, six mechanical springs are integrated to enhance the opening force, overcoming any underpressure at the door. The ventilation flaps extend 200 mm into the escape route when open, while the mechanism protrudes 52.5 mm inward.

Technology Explained Simply
The door is controlled via the CMC III Door Control Module (DCM). Power supply is provided by the DCM, with a rated voltage of 24 V DC and a rated current of 780 mA (0.78 A). The control enables remote operation via the CMC III system. The door is designed for operation in a temperature range of -5 °C to +45 °C and relative humidity of 5 % to 95 % (non-condensing). The door hinge direction is standard right-hand, but can be changed from right to left for single doors.

Compatibility and Accessories
The viewing door is intended for mounting on VX IT racks. Operation requires connection to the Door Control Module 7030.501. The door is equipped with a comfort handle for half cylinder with safety lock 3524 E. Suitable accessories include, for example, earthing straps M8-M8, comfort handles in various versions, enclosure keys, profile rails, and safety locking devices. The use of front and rear doors of the ADO system is always required.

Mounting and Installation
The door is mounted on VX IT racks and requires connection to the CMC III Door Control Module. The connection cable has a length of 2.5 m from the door hinge. Mounting is performed without modifying the existing lock system. Manual opening of the door does not affect the function of the ventilation flaps.

Operational Advantages
The automatic opening of the ventilation flaps in an emergency enables a rapid response to disruptions in cooling or fire suppression system operation. The use of room air for emergency cooling or direct supply of fire suppressant gas into the enclosure enhances the safety and reliability of the IT infrastructure. The robust construction from aluminium extruded profile and single-pane safety glass ensures high stability and safety. The door is suitable for use in IT environments with high requirements for safety and reliability.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/593705
qrcode für Rittal 7030262 sight door VX IT with emergency ventilation