| General |
| Colour | RAL 7035 Structure |
| Scope of delivery | Complete plug-and-play unit (pluggable terminal block), multilingual documentation |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Degree of protection IP according to EN 60 529 | IP 24, IP 54 (electrical) |
| Total cooling capacity according to DIN EN 14511 Tw18 / Tu35 | Cooling capacity Tw18 Tu35/50 Hz: 7 kW, Cooling capacity Tw18 Tu35/60 Hz: 6.9 kW |
| Rated operating voltage | 380 V - 415 V, 3~, 50 Hz, 440 V - 480 V, 3~, 60 Hz |
| Width | 450 mm |
| Height | 1.020 mm |
| Depth | 710 mm |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software in accordance with these license terms. |
| Temperature control | e+ controller (factory setting +20 °C) |
| Operating temperature range | -5 °C...50 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range of cooling medium | 5 °C...35 °C |
| Temperature hysteresis | ± 0,5 K |
| Refrigerant/cooling medium | Refrigerant: R-513A, Quantity: 1.5 kg, Global Warming Potential (GWP): 631, CO₂ equivalent (CO₂e): 0.95 t |
| Flow rate (coolant medium) | At 50 Hz: 20 l/min |
| Rated power Pel | At 50 Hz: 2.84 kW, At 60 Hz: 3.07 kW |
| Rated current max. | At 50 Hz: 4.28 A, At 60 Hz: 4.1 A |
| Fuse | Circuit breaker/fuse: 15 A |
| Cooling performance factor (EER) 50 Hz Tw18 / Tu35 DIN EN 14511 | 2,77 |
| Water circuit | Open |
| Water connections | ¾" IG |
| Number of refrigeration circuits | 1 |
| Tank | Material: plastic PE, volume: 12 l |
| Operating weight | 120 kg |
The Rittal Blue e+ Chiller type SK 3334450 is an industrial chiller for central cooling of fluid media, particularly for air/water heat exchangers in enclosures and industrial systems. The unit features a total cooling capacity of 7.0 kW at 50 Hz and 6.9 kW at 60 Hz, measured according to DIN EN 14511 under conditions Tw18 / Tu35. The cooling performance is achieved through DC inverter technology, enabling variable speed operation and up to 70 % energy savings compared to conventional systems. The operating voltage covers two ranges: 380 V to 415 V, 3~, 50 Hz and 440 V to 480 V, 3~, 60 Hz, allowing worldwide use without rewiring. Temperature control is managed via an e+ controller, factory-set to +20 °C with a temperature hysteresis of ± 0.5 K, ensuring high temperature accuracy.
Applications
The chiller is designed for use in industrial environments where continuous and precise cooling of fluid media is required. It is commonly used for cooling enclosures, control systems, or other electronic components cooled via air/water heat exchangers. The operating temperature of the unit ranges from -5 °C to 50 °C, with the coolant operating between 5 °C and 35 °C. Storage temperature can reach up to -40 °C and 70 °C, enabling flexible storage conditions.
Functions and Equipment in Detail
The unit includes an integrated over-flow valve and monitoring sensors for maximum safety. Operation is via a touch display, enabling intuitive control and display of operating parameters. Integrated communication interfaces support networking and remote monitoring. For remote monitoring and networking of the Blue e+ device generation, the IoT Interface with article number 3124.300 is available, enabling monitoring of device data, statuses, and system messages. The pumps are equipped with high-efficiency IE3 motors, further enhancing energy efficiency.
Technology Explained Simply
The chiller operates with refrigerant R-513A, containing 1.5 kg with a Global Warming Potential (GWP) of 631. The CO₂ equivalent is 0.95 t. The water circuit is open, with water connections having a diameter of ¾" IG. The coolant flow rate is 20 l/min at 50 Hz. The nominal power (Pel) is 2.84 kW (50 Hz) or 3.07 kW (60 Hz), and the maximum rated current is 4.28 A (50 Hz) or 4.1 A (60 Hz). The coefficient of performance (EER) is 2.77 at 50 Hz under conditions Tw18 / Tu35 according to DIN EN 14511. The tank is made of PE plastic and has a volume of 12 l.
Compatibility and Accessories
Various accessories are available to extend functionality and maintenance. These include levelling feet M12 with an adjustment height of 18–43 mm, balancing valves for air/water heat exchangers in sizes 3/4x3 and 3/4x1, and various Rifrost products for water circuits (Rifrost-Outdoor 10 L, 25 L and Rifrost-Standard 10 L, 25 L). Additionally, pleated filters, metal filters, and filter mats are available for the Blue e+ chiller series. Double swivel castors M12 (2 each with/without brake) and an adjustable cross-brace for depths of 600/800 mm support installation and mobility. An SK temperature sensor for Blue e+ cooling units enables precise temperature monitoring.
Mounting and Installation
The chiller is designed as a compact unit with dimensions W x H x D 450 mm × 1,020 mm × 710 mm. The unit is delivered ready for connection and features a plug-in connection terminal strip, simplifying installation. Protection rating IP 24 (general) and IP 54 (electrical) according to EN 60 529 ensures protection against contact and splashing water, allowing use even in damp environments. The pre-fuse is implemented as a fuse switch disconnector/fuse with 15 A.
Operational Advantages
Operation of the Blue e+ chiller is particularly energy-efficient due to inverter technology and variable speed components. Integrated sensors and the touch display enable easy operation and monitoring. Multi-voltage capability without rewiring facilitates worldwide use. The compact design minimizes required floor space. Integrated monitoring and remote monitoring via the IoT Interface increase machine availability and process safety. The unit is designed for use in industrial systems where reliable and precise cooling is required.
Scope of Delivery
The delivery includes a fully ready-to-connect unit with plug-in connection terminal strip and multilingual documentation. The unit is prepared for direct operation and requires no additional mounting components for commissioning.