| General |
| Model | Wall surface mounted |
| Material | Stainless steel 1.4404 (AISI 316L) |
| Colour | RAL 7001 |
| Scope of delivery | Condenser with hydrophobic RiNano coating, pre-wired (pluggable terminal block), drilling template, mounting material, integrated electrical condensate evaporation |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 1.6 kW, cooling capacity L35 L35/60 Hz: 1.73 kW, cooling capacity L35 L50/50 Hz: 1.18 kW, cooling capacity L35 L50/60 Hz: 1.26 kW |
| Rated operating voltage | 115 V, 1~, 50 Hz/60 Hz |
| Rated current max. | At 50 Hz: 11.5 A, At 60 Hz: 12.5 A |
| Inrush current (max.) | At 50 Hz: 26 A, At 60 Hz: 28 A |
| Air performance (free blowing) | External circuit: 805 m³/h, internal circuit: 585 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling capacity ratio L35 L35 (EER) 50 Hz: 1.83, Cooling capacity ratio L35 L35 (EER) 60 Hz: 1.79 |
| Width | 405 mm |
| Height | 1.020 mm |
| Depth | 358 mm |
| Degree of protection IP according to EN 60 529 | External circuit IP 34, internal circuit IP 55 |
| NEMA degree of protection | NEMA 4X |
| Refrigerant/cooling medium | Refrigerant: R-513A, Quantity: 0.61 kg, Global Warming Potential (GWP): 631, CO₂ Equivalent (CO₂e): 0.38 t |
| Temperature control | e-Comfortcontroller (factory setting +35 °C) |
| Operating temperature range | 10 °C...55 °C |
| Storage temperature range | -40 °C...70 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 0.87 kW, rated power L35 L35/60 Hz: 0.96 kW, rated power L35 L50/50 Hz: 0.91 kW, rated power L35 L50/60 Hz: 1 kW |
| Permissible operating pressure (p max.) | 25 bar |
| Fuse | Transformer protection switch: 14...20 A |
The Rittal SK 3305514 is a wall-mounted cooling unit of the Blue e-Series, specifically designed for climate control of enclosures in industrial environments. It features a cooling capacity of up to 1.73 kW at 60 Hz and 1.6 kW at 50 Hz, with the exact performance depending on operating frequency and ambient temperature. The unit operates at a rated voltage of 115 V, 1~, 50/60 Hz, making it suitable for applications in regions with different power supply standards. The maximum cooling capacity is achieved under standard conditions L35 L35 (external temperature 35 °C, internal temperature 35 °C). The nominal power is 0.87 kW at 50 Hz and 0.96 kW at 60 Hz, resulting in energy efficiency with an EER value of 1.83 (50 Hz) and 1.79 (60 Hz). The air flow rate is 805 m³/h in the external circuit and 585 m³/h in the internal circuit, ensuring efficient air circulation within the enclosure.
Applications
This cooling unit is suitable for use in industrial applications such as machine building, automation technology, or process control systems. The protection rating NEMA 4X and IP classification (external circuit IP 34, internal circuit IP 55) make it robust against dust, splashing water, and light spray, allowing use even outdoors or in humid environments. The operating temperature range is between 10 °C and 55 °C, enabling operation under various climatic conditions. The storage temperature range extends from -40 °C to 70 °C, allowing safe storage even under extreme conditions.
Features and Equipment in Detail
The unit is standard-equipped with an e-Comfort controller, factory-set to a temperature of +35 °C. The adjustable range is 20 °C to 50 °C, allowing individual temperature adjustment within the enclosure. The integrated electric condensate evaporation system ensures that condensate formed during operation evaporates automatically, eliminating the need for an external drain. The condenser is coated with a hydrophobic RiNano coating, improving heat transfer and simplifying cleaning. The unit is pre-wired with a plug-in connection terminal strip, simplifying installation. The delivery includes a drilling template and mounting materials.
Technology Explained Simply
The cooling unit operates with refrigerant R-513A, which has a lower environmental impact than conventional refrigerants. The quantity is 0.61 kg, with a Global Warming Potential (GWP) of 631 and a CO₂ equivalent of 0.38 t. The maximum operating pressure is 25 bar, ensuring system safety. The pre-fuse is implemented as a transformer protection switch with a nominal value of 14 to 20 A, limiting the inrush current (maximum 26 A at 50 Hz, 28 A at 60 Hz). Dimensions are 405 mm (width) × 1,020 mm (height) × 358 mm (depth), enabling compact wall mounting.
Compatibility and Accessories
The cooling unit is networkable via the IoT Interface, requiring a Blue e IoT Adapter. This enables remote monitoring and control of the unit over a network. Compatible accessories include, among others, a VX support roller, a door position switch, an SK Master/Slave cable for the SK-Bus system, and an SK air deflector for models SK 3304/3305. These components support integration into existing automation systems and enhance enclosure functionality.
Mounting and Installation
Wall mounting is performed using the included mounting materials and drilling template. The connected terminal strip allows for quick and secure connection to the power supply. Installation requires no additional tools or components, as the unit is delivered ready for connection. The integrated condensate evaporation eliminates the need for an external drain, simplifying installation.
Operational Advantages
The unit is characterized by high energy efficiency and robust construction. The use of stainless steel 1.4404 (AISI 316L) ensures corrosion resistance, especially in humid or aggressive environments. The integrated condensate evaporation reduces maintenance effort, as no condensate needs to be drained. Network capability via the IoT Interface enables remote monitoring and control, simplifying operational control and optimization. The protection rating NEMA 4X and IP classification ensure reliable operation even under challenging environmental conditions.